M A I N T E N A N C E
112 / 192
XS20000_31_manual_ger_eng_it_V1.1.2.doc
R. Kistler
Figure 28: Removing the front cover of the UPS system
2. Disconnect the internal battery plug connections of the individ-
ual battery module inserts and remove the battery cover by
releasing both upper screws (see Figure 29).
Figure 29: Remove the battery cover
3. Pull out the individual battery module inserts.
NOTE
Check whether the replacement batteries have the same
specifications as the old batteries.
4. Replace the batteries in the battery module insert. Please read
the "
Disposing of old batteries or the UPS system"
section for
information on proper disposal.
Battery cover
Battery
plug connection
Screws