12
GENSET
LOAD WATERLINE
MUFFLER
WATER-EXHAUST MIXER LEVEL
SEE OUTLINE DRAWING (PAGE 23)
48 INCH
(1.2 METER)
MAX.
12 INCH
(305 MM)
MIN.
MUST BE ABOVE
WATERLINE
SIPHON BREAK
NOT
REQUIRED WHEN WATER-EXHAUST
MIXER IS
AT LEAST 6 INCHES (152 MM) ABOVE
LOAD WATER LINE
12 INCH
(305 MM)
MIN.
Note: All exhaust hose and pipe must slope, without sagging, at least 1/2 inch per foot (42 mm/meter).
FIGURE 3. TYPICAL INSTALLATION ABOVE LOAD WATERLINE—WITH MUFFLER AND RESONATOR