Changing Frequency and Adjusting Voltage

CHANGING FREQUENCY

Model MGKBC gensets may be configured to oper-
ate at 60 Hz or 50 Hz. To change the operating fre-
quency, remove the front access door and find wir-
ing harness connectors 

P5

P6

 and 

P7

 (Page  21),

which are located just behind the ignition coil. Con-
nect

 P5 

to 

P6 

for 

60 HZ

 or 

P5 

to 

P7

 for 

50 HZ

.

Note 1: When changing genset operating frequency,
make sure the line circuit breakers are suitable for
the new output. Replace them if necessary with ones
of appropriate rating.

Note 2: Check and adjust voltage as necessary after
frequency has been changed.

ADJUSTING VOLTAGE

WARNING

HAZARDOUS VOLTAGE! Touching

uninsulated live parts inside the genset or con-
nected equipment can result in severe personal
injury or death. For your protection, stand on a
dry wooden platform or rubber insulating mat,
make sure your clothing and shoes are dry, re-
move jewelry from your hands and use tools
with insulated handles.

Before adjusting voltage, make sure that proper
fuel, exhaust, raw water and battery connections
have been made and that the engine has the proper
levels of oil and coolant. See the Operator’s Manu-
al. Complete 

Installation Checks and Startup

(Page 20) as far as possible. Disconnect all genera-
tor loads and connect accurate meters to measure
AC voltage and frequency.

Using Start Switch

1. Start the genset and let voltage and frequency

stabilize for 5 to 10 seconds.

2. Rapidly press 

START 

6 times 

during the first

minute after startup 

to put the genset controller

into 

voltage adjust mode

. The amber status

light will begin blinking about once every sec-
ond to indicate the change to voltage adjust
mode. The green status light will remain on.

3.

To adjust voltage up

, press and quickly re-

lease 

START

. Voltage will increase approxi-

mately 0.6 volts each press and release.

4.

To adjust voltage down

, press and hold

START 

for about 1 second. Voltage will de-

crease approximately 0.6 volts each press and
release.

5. When satisfied with the adjustment, wait about

20 seconds for the amber light to stop blinking
and then press 

STOP

 to save the adjustment.

6. Restart the genset and check voltage.

Using e-Series Digital Display

See the Operator’s Manual for details regarding the

e-Series Digital Display

.

1. Start the genset and let voltage and frequency

stabilize for 5 to 10 seconds.

2. Rapidly press 

START 

6 times 

during the first

minute after startup 

to put the genset controller

into 

voltage adjust mode

. The green status light

will begin blinking about once every second
and the Display will indicate a Status change
from 

Running 

to 

Volt Adj 

(Figure 7).

3.

To adjust voltage up

, press and quickly re-

lease 

START

. Voltage will increase approxi-

mately 0.6 volts each press and release.

4.

To adjust voltage down

, press and hold

START 

for about 1 second. Voltage will de-

crease approximately 0.6 volts each press and
release.

5. When satisfied with the adjustment, wait about

20 seconds for the Display to indicate a Status
change from 

Volt Adj

 to 

Running

 and then

press 

STOP

 to save the adjustment.

6. Restart the genset and check voltage.

Volt Adj

FIGURE 7. VOLTAGE ADJUSTMENT SCREEN

Redistribution or publication of this document, 

by any means, is strictly prohibited.

Содержание MGKBC Series

Страница 1: ...Caution This document contains mixed page sizes 8 5 x 11 or 11 x 17 which may affect printing Please adjust your printer settings according to the size of each page you wish to print...

Страница 2: ...Installation Manual MGKBC MGKBD Printed in U S A 02 04 981 0635B Redistribution or publication of this document by any means is strictly prohibited...

Страница 3: ...aust from this product contains chemicals known to the State of California to cause cancer birth defects or other reproductive harm Redistribution or publication of this document by any means is stric...

Страница 4: ...tion Protection 4 FUEL SUPPLY 5 ENGINE COOLING 6 Cooling System Overview 6 System Components 7 Raw Water Pickup Test 8 ENGINE EXHAUST 9 System Components 9 Exhaust Water Separator Backflow Test 10 ELE...

Страница 5: ...genset drip pan and compartment clean Oily rags can catch fire Gear stowed in the compartment can cause the genset to over heat Make sure all fasteners are secure and proper ly torqued Do not work on...

Страница 6: ...e present or in areas sharing ventilation with fuel tanks en gines and other such equipment Keep flames sparks pilot lights electrical switches arc pro ducing equipment and all other sources of igni t...

Страница 7: ...plied greatly by the station wagon effect obstructions that block exhaust dissipation and infiltration from neighbor ing boats To protect against all three situations Onan recommends that reliable CO...

Страница 8: ...13 liter min 3 0 gpm 16 liter min 3 5 gpm 13 liter min Raw Water Flow 60 Hz 50 Hz 5 0 gpm 19 liter min 4 0 gpm 15 liter min 5 0 gpm 19 liter min Maximum Raw Water Pump Lift 4 feet 1 2 m with 5 8 inch...

Страница 9: ...vi This page is intended to be blank Redistribution or publication of this document by any means is strictly prohibited...

Страница 10: ...G regulations is mandatory for boats in U S waters The American Boat and Yacht Council ABYC and the National Fire Protection Associa tion NFPA are typical of agencies that publish safety standards for...

Страница 11: ...ex changer and replace the fuel pump At least 1 inch 25 mm of clearance is required in front of the outlet air grille on the right side There must be access for Starting and stopping the genset Resett...

Страница 12: ...ct that WARNING Gasoline vapors can explode Be fore starting the genset operate the exhaust blower for 4 minutes and check the genset compartment and bilge for gasoline vapors Ventilation Ducts Ventil...

Страница 13: ...heads for wiring conduit pipe and hose must be sealed to prevent exhaust gases and gasoline vapors from entering the rest of the boat Wiring conduit must be sealed inside as well as outside Plumbing F...

Страница 14: ...in the fuel tank for the genset The inside diameter should be 1 4 inch 6 35 mm It must not be greater than 3 8 inch 9 mm In a common fuel supply tank the genset pickup tube should be shorter than tho...

Страница 15: ...es The raw water is expelled from the boat along with the exhaust gases The V belt drives the coolant and the raw water pumps RAW WATER IN EXHAUST RAW WATER OUT THERMOSTAT HOUSING BLOCK DRAIN CAP RAW...

Страница 16: ...engine A rear facing scoop can develop enough suction to impede flow Siphon Break Conduct the RAW WATER PICKUP TEST to deter mine whether a siphon break is required to prevent the engine from being f...

Страница 17: ...rk the level on the genset enclosure 3 Operate the boat through its speed range for ward and reverse While the boat is operating have someone monitor the water level in the hose and mark the highest l...

Страница 18: ...d stainless steel el bows are available from Onan Horizontal runs of hose must slope down at least 1 2 inch per foot 42 mm meter and be supported such that there are no sags The entire run of hose mus...

Страница 19: ...linders become flooded The sea trials must verify that there is no backflow through either the exhaust hull fitting or the wa ter separator drain hose fitting Other Engine Exhaust Systems Do not T int...

Страница 20: ...be able to look for water discharge from the hull to tell whether engine exhaust cooling water is flowing However the genset will shutdown if water stops flowing Code No 7 See Troubleshooting in the...

Страница 21: ...MIN MUST BE ABOVE WATERLINE SIPHON BREAK NOT REQUIRED WHEN WATER EXHAUST MIXER IS AT LEAST 6 INCHES 152 MM ABOVE LOAD WATER LINE 12 INCH 305 MM MIN Note All exhaust hose and pipe must slope without s...

Страница 22: ...HAN 6 INCHES 152 MM ABOVE LOAD WATER LINE Notes 1 All exhaust hose and pipe must slope without sagging at least 1 2 inch per foot 42 mm meter 2 The operator will not be able to look for water discharg...

Страница 23: ...H 305 MM MIN 12 INCH 305 MM MIN MUST BE ABOVE WATERLINE SIPHON BREAK REQUIRED WHEN WATER EXHAUST MIXER IS BELOW OR LESS THAN 6 INCHES 152 MM ABOVE LOAD WATER LINE Note All exhaust hose and pipe must s...

Страница 24: ...ge fre quency or to readjust voltage Grounding The genset power supply wiring and all connected electrical equipment must be bonded to the com mon grounding system of the boat in accordance with appli...

Страница 25: ...tal Displays must have eight 8 conductors Harnesses for remote switches and meters only must have at least six 6 conductors connector pins 7 and 8 are not used See Figure 6 Note 1 All feed through hol...

Страница 26: ...se vere personal injury The battery compartment must be ventilated and isolated from spark pro ducing equipment Battery Cables Size battery cables according to Table 2 Total cable length is the sum of...

Страница 27: ...ctory Jumpers The genset leaves the factory with SWB jumpered to the other two connectors ESTOP and CO Leave the jumpers connected when no external shutdown devices are to be connected otherwise the g...

Страница 28: ...e genset controller into voltage adjust mode The amber status light will begin blinking about once every sec ond to indicate the change to voltage adjust mode The green status light will remain on 3 T...

Страница 29: ...ion and filling The entire exhaust system is accessible for in spection and replacement Fuel tanks piping hoses and filters comply with regulations and are accessible for inspec tion and replacement T...

Страница 30: ...21 630 2528 FIGURE 8 WIRING DIAGRAM...

Страница 31: ...22 630 252 FIGURE 9 GENERATOR CONNECTION DIAGRAM...

Страница 32: ...23 500 3363 FIGURE 10 OUTLINE DRAWING...

Отзывы: