14
GENSET
LOAD WATERLINE
MUFFLER
SIPHON
BREAK
VALVE
WATER-EXHAUST MIXER LEVEL
SEE OUTLINE DRAWING (PAGE 23)
48 INCH
(1.2 METER)
MAX.
12 INCH
(305 MM)
MIN.
12 INCH
(305 MM)
MIN.
12 INCH
(305 MM)
MIN.
MUST BE ABOVE
WATERLINE
SIPHON BREAK REQUIRED WHEN WATER-EXHAUST MIXER IS
BELOW OR LESS THAN 6 INCHES (152 MM) ABOVE
LOAD WATER LINE
Note: All exhaust hose and pipe must slope, without sagging, at least 1/2 inch per foot (42 mm/meter).
FIGURE 5. TYPICAL INSTALLATION BELOW LOAD WATERLINE—WITH A SIPHON BREAK, MUFFLER AND RESONATOR