background image

7

SYSTEM COMPONENTS

Raw Water Pump

The raw water pump can work against a maximum
lift (suction) of 48 inches (122 cm) WC to deliver the
required flow of cooling water. Lift is a combination
of the actual vertical lift and the resistance to flow
cause by the hose, strainer, sea cock and through-
hull fitting.

The pump impeller must be wetted with water to es-
tablish initial pump lubrication and suction. See the
Operator’s Manual.

Raw Water Hose

The 5/8 inch (15.9 mm) hose barb for raw water
pickup is mounted on the drip pan on the right side
(Page  23). Use SAE 20R3 or equivalent hose to
supply raw water to the genset. The hose must be
able to resist a slight vacuum.

Sea Water Strainer

The sea water strainer should have a 5/8 inch
(15.9 mm) inlet. It should be located below the level
of the raw water pump (Page  23) and as close as
possible to the genset. The basket must be remove-
able for cleaning.

Sea Cock

Install a bronze, full-flow sea cock on the through-
hull fitting.

Through-Hull Fitting and Strainer

The through-hull fitting should have a 5/8 inch (15.9
mm) inlet and be as close to the genset as possible.
If the strainer has slotted openings, the slots must
be parallel to the keel for best flow when the boat is
under way. Also, stagger the through-hull fittings
along the keel so that downstream fittings are not
starved.

CAUTION

Do not use a scoop-type through-

hull fitting. A forward-facing scoop can develop
enough ram pressure to flood the engine. A
rear-facing scoop can develop enough suction
to impede flow.

Siphon Break

Conduct the RAW WATER PICKUP TEST to deter-
mine whether a siphon break is required to prevent
the engine from being flooded with floatation water.
Siphon Break Kit 541-0876 is available if a siphon
break is required. Carefully follow the instructions in
the kit. The hoses in the kit replace the hose be-
tween the engine heat exchanger and exhaust-wa-
ter mixer (Figure 1). The end panel of the genset
has knockouts for the hoses to pass through
(Page  23). The kit has the hole grommets. Fig-
ures 4 and 5 illustrate typical siphon break installa-
tions.

CAUTION

Engine damage due to flooding as a

result of failing to install a required siphon break
is not covered by Warranty.

Coolant Recovery Tank

The genset is shipped with a coolant recovery tank
kit. Follow the instructions in the kit. 

The tank must

be accessible for daily inspection and refilling.

Clamp the recovery hose to the hose barb on the
coolant fill neck (Figure 1). Route the tank recovery
and overflow hoses through the holes in the end of
the enclosure (Page  23). Make sure the overflow
hose terminates in the drip pan where it will not
splash coolant on electrical components. Fill the
tank in accordance with the Operator’s Manual.

Initial Coolant Fill

The genset is normally shipped from the factory with
coolant, unless prohibited by shipping regulations.
Fill the system, if necessary, in accordance with the
Operator’s Manual.

CAUTION

Engine damage due to running the

engine without coolant is not covered by War-
ranty.

Redistribution or publication of this document, 

by any means, is strictly prohibited.

Содержание MGKBC Series

Страница 1: ...Caution This document contains mixed page sizes 8 5 x 11 or 11 x 17 which may affect printing Please adjust your printer settings according to the size of each page you wish to print...

Страница 2: ...Installation Manual MGKBC MGKBD Printed in U S A 02 04 981 0635B Redistribution or publication of this document by any means is strictly prohibited...

Страница 3: ...aust from this product contains chemicals known to the State of California to cause cancer birth defects or other reproductive harm Redistribution or publication of this document by any means is stric...

Страница 4: ...tion Protection 4 FUEL SUPPLY 5 ENGINE COOLING 6 Cooling System Overview 6 System Components 7 Raw Water Pickup Test 8 ENGINE EXHAUST 9 System Components 9 Exhaust Water Separator Backflow Test 10 ELE...

Страница 5: ...genset drip pan and compartment clean Oily rags can catch fire Gear stowed in the compartment can cause the genset to over heat Make sure all fasteners are secure and proper ly torqued Do not work on...

Страница 6: ...e present or in areas sharing ventilation with fuel tanks en gines and other such equipment Keep flames sparks pilot lights electrical switches arc pro ducing equipment and all other sources of igni t...

Страница 7: ...plied greatly by the station wagon effect obstructions that block exhaust dissipation and infiltration from neighbor ing boats To protect against all three situations Onan recommends that reliable CO...

Страница 8: ...13 liter min 3 0 gpm 16 liter min 3 5 gpm 13 liter min Raw Water Flow 60 Hz 50 Hz 5 0 gpm 19 liter min 4 0 gpm 15 liter min 5 0 gpm 19 liter min Maximum Raw Water Pump Lift 4 feet 1 2 m with 5 8 inch...

Страница 9: ...vi This page is intended to be blank Redistribution or publication of this document by any means is strictly prohibited...

Страница 10: ...G regulations is mandatory for boats in U S waters The American Boat and Yacht Council ABYC and the National Fire Protection Associa tion NFPA are typical of agencies that publish safety standards for...

Страница 11: ...ex changer and replace the fuel pump At least 1 inch 25 mm of clearance is required in front of the outlet air grille on the right side There must be access for Starting and stopping the genset Resett...

Страница 12: ...ct that WARNING Gasoline vapors can explode Be fore starting the genset operate the exhaust blower for 4 minutes and check the genset compartment and bilge for gasoline vapors Ventilation Ducts Ventil...

Страница 13: ...heads for wiring conduit pipe and hose must be sealed to prevent exhaust gases and gasoline vapors from entering the rest of the boat Wiring conduit must be sealed inside as well as outside Plumbing F...

Страница 14: ...in the fuel tank for the genset The inside diameter should be 1 4 inch 6 35 mm It must not be greater than 3 8 inch 9 mm In a common fuel supply tank the genset pickup tube should be shorter than tho...

Страница 15: ...es The raw water is expelled from the boat along with the exhaust gases The V belt drives the coolant and the raw water pumps RAW WATER IN EXHAUST RAW WATER OUT THERMOSTAT HOUSING BLOCK DRAIN CAP RAW...

Страница 16: ...engine A rear facing scoop can develop enough suction to impede flow Siphon Break Conduct the RAW WATER PICKUP TEST to deter mine whether a siphon break is required to prevent the engine from being f...

Страница 17: ...rk the level on the genset enclosure 3 Operate the boat through its speed range for ward and reverse While the boat is operating have someone monitor the water level in the hose and mark the highest l...

Страница 18: ...d stainless steel el bows are available from Onan Horizontal runs of hose must slope down at least 1 2 inch per foot 42 mm meter and be supported such that there are no sags The entire run of hose mus...

Страница 19: ...linders become flooded The sea trials must verify that there is no backflow through either the exhaust hull fitting or the wa ter separator drain hose fitting Other Engine Exhaust Systems Do not T int...

Страница 20: ...be able to look for water discharge from the hull to tell whether engine exhaust cooling water is flowing However the genset will shutdown if water stops flowing Code No 7 See Troubleshooting in the...

Страница 21: ...MIN MUST BE ABOVE WATERLINE SIPHON BREAK NOT REQUIRED WHEN WATER EXHAUST MIXER IS AT LEAST 6 INCHES 152 MM ABOVE LOAD WATER LINE 12 INCH 305 MM MIN Note All exhaust hose and pipe must slope without s...

Страница 22: ...HAN 6 INCHES 152 MM ABOVE LOAD WATER LINE Notes 1 All exhaust hose and pipe must slope without sagging at least 1 2 inch per foot 42 mm meter 2 The operator will not be able to look for water discharg...

Страница 23: ...H 305 MM MIN 12 INCH 305 MM MIN MUST BE ABOVE WATERLINE SIPHON BREAK REQUIRED WHEN WATER EXHAUST MIXER IS BELOW OR LESS THAN 6 INCHES 152 MM ABOVE LOAD WATER LINE Note All exhaust hose and pipe must s...

Страница 24: ...ge fre quency or to readjust voltage Grounding The genset power supply wiring and all connected electrical equipment must be bonded to the com mon grounding system of the boat in accordance with appli...

Страница 25: ...tal Displays must have eight 8 conductors Harnesses for remote switches and meters only must have at least six 6 conductors connector pins 7 and 8 are not used See Figure 6 Note 1 All feed through hol...

Страница 26: ...se vere personal injury The battery compartment must be ventilated and isolated from spark pro ducing equipment Battery Cables Size battery cables according to Table 2 Total cable length is the sum of...

Страница 27: ...ctory Jumpers The genset leaves the factory with SWB jumpered to the other two connectors ESTOP and CO Leave the jumpers connected when no external shutdown devices are to be connected otherwise the g...

Страница 28: ...e genset controller into voltage adjust mode The amber status light will begin blinking about once every sec ond to indicate the change to voltage adjust mode The green status light will remain on 3 T...

Страница 29: ...ion and filling The entire exhaust system is accessible for in spection and replacement Fuel tanks piping hoses and filters comply with regulations and are accessible for inspec tion and replacement T...

Страница 30: ...21 630 2528 FIGURE 8 WIRING DIAGRAM...

Страница 31: ...22 630 252 FIGURE 9 GENERATOR CONNECTION DIAGRAM...

Страница 32: ...23 500 3363 FIGURE 10 OUTLINE DRAWING...

Отзывы: