Setting Hold Functions
ZX-GT User’s Manual
3
FUNCTION SETTINGS
73
Setting Hold Functions
Set hold conditions for measured values. The hold functions hold data for specific points,
such as the minimum or maximum value, during the sampling period (sampling time), and
output those values at the end of the sampling period.
Hold
Setting value
Description
OFF
Hold measurement is not performed. The measured value is output
at all times. (default value)
P-H (Peak hold)
The maximum value is held during the sampling period. The output
changes at the end of the sampling period, and is held until the end
of the next sampling period.
B-H (Bottom hold)
The minimum value is held during the sampling period. The output
changes at the end of the sampling period, and is held until the end
of the next sampling period.
SMPLE (Sample hold)
The measured value is held at the start of the sampling period. The
output changes at the start of the sampling period and is held until
the start of the next sampling period.
Sampling period
Current
measured value
Output
Maximum
value
Sampling period
Current
measured value
Output
Minimum
value
Sampling period
Current
measured value
Output
zx_gt.book Page 73 Wednesday, May 30, 2007 3:29 PM
Содержание ZX-GT -
Страница 1: ...Smart Sensor Cat No Z263 E1 01 ZX GT Series USER S MANUAL...
Страница 12: ...ZX GT User s Manual 10 MEMO...
Страница 17: ...CONTENTS ZX GT User s Manual 15 MEMO...
Страница 20: ...Operation Step Guide ZX GT User s Manual 18 MEMO...
Страница 42: ...Initializing Controller Settings ZX GT User s Manual 40 MEMO...
Страница 50: ...Functions and Operations during Operation RUN Mode 48 ZX GT User s Manual MEMO...
Страница 74: ...Setting Output Conditions ZX GT User s Manual 72 5 Check that setting of correction values is completed SUB...
Страница 90: ...Special Functions ZX GT User s Manual 88 MEMO...
Страница 157: ...Compliance with EC Directives ZX GT User s Manual 5 APPENDICES 155 MEMO...
Страница 162: ...Quick Reference for Displays ZX GT User s Manual 160 MEMO...