16
Specifications
Section 2-1
2-1-3
Input Specifications
A switch on the front of the Unit (pin 3 of the DIP switch) selects whether the
Temperature Control Unit’s data is stored and indicated as 4-digit BCD or
binary (i.e., 4-digit hexadecimal). Pin 2 of the DIP switch selects whether the
temperature is indicated in
°
C or
°
F.
The indicated range will be within ±20
°
C or ±20
°
F of the setting ranges shown
in the following table. (See note 1.)
Thermocouple Input
Setting Ranges
Platinum Resistance
Thermometer Input
Setting Ranges
Note
1.
If the allowed indication range is exceeded, a sensor error will occur, the
corresponding Sensor Error Flag will be turned ON, and the PV will contain
the data “CCCC.” When a sensor error occurs, that control loop’s control
output will be turned OFF. The alarm function will operate because the PV
indicates an abnormally high temperature.
No.
Thermocouple type
Range in
°
C Range
in
°
F
Binary (4-digit Hex)
4-digit BCD
Binary (4-digit Hex)
4-digit BCD
0
K:
−
200 to 1,300
°
C
(
−
300 to 2,300
°
F)
FF38 to FFFF to 0514
(
−
200 to
−
1 to 1,300)
F200 to 1300
(
−
200 to 1,300)
FED4 to FFFF to 08FC
(
−
300 to
−
1 to 2,300)
F300 to 2300
(
−
300 to 2,300)
1
K: 0.0 to 500
°
C
(0.0 to 900.0
°
F)
0000 to 1388
(0.0 to 500.0)
0000 to 5000
(0.0 to 500.0)
0000 to 2328
(0.0 to 900.0)
0000 to 9000
(0.0 to 900.0)
2
J:
−
100 to 850
°
C
(
−
100 to 1,500
°
F)
FF9C to FFFF to 0352
(
−
100 to
−
1 to 850)
F100 to 0850
(
−
100 to 850)
FF9C to FFFF to 05DC
(
−
100 to
−
1 to 1,500)
F100 to 1500
(
−
100 to 1,500)
3
J: 0.0 to 400
°
C
(0.0 to 750.0
°
F)
0000 to 0FA0
(0.0 to 400.0)
0000 to 4000
(0.0 to 400.0)
0000 to 1D4C
(0.0 to 750.0)
0000 to 7500
(0.0 to 750.0)
4
T:
−
200.0 to 400.0
°
C
(
−
300.0 to 700.0
°
F)
F830 to FFFF to 0FA0
(
−
200.0 to
−
0.1 to 400.0)
F999 to 4000
(
−
99.9 to 400.0)
See note 3.
F448 to FFFF to 1B58
(
−
300.0 to
−
0.1 to 700.0)
F999 to 7000
(
−
99.9 to 700.0)
See note 3.
5
L:
−
100 to 850
°
C
(
−
100 to 1,500
°
F)
FF9C to FFFF to 0352
(
−
100 to
−
1 to 850)
F100 to 0850
(
−
100 to 850)
FF9C to FFFF to 05DC
(
−
100 to
−
1 to 1,500)
F100 to 1500
(
−
100 to 1,500)
6
L: 0.0 to 40
°
C
(0.0 to 750.0
°
F)
0000 to 0FA0
(0.0 to 400.0)
0000 to 4000
(0.0 to 400.0)
0000 to 1D4C
(0.0 to 750.0)
0000 to 7500
(0.0 to 750.0)
7
R: 0 to 1,700
°
C
(0 to 3,000
°
F)
0000 to 06A4
(0 to 1,700)
0000 to 1700
(0.0 to 1,700)
0000 to 0BB8
(0 to 3,000)
0000 to 3000
(0.0 to 3,000)
8
S: 0 to 1,700
°
C
(0 to 3,000
°
F)
0000 to 06A4
(0 to 1,700)
0000 to 1700
(0.0 to 1,700)
0000 to 0BB8
(0 to 3,000)
0000 to 3000
(0.0 to 3,000)
9
B: 100 to 1,800
°
C
(300 to 3,200
°
F)
See note 2.
0064 to 0708
(100 to 1,800)
0100 to 1800
(100 to 1,800)
012C to 0C80
(300 to 3,200)
0300 to 3200
(300 to 3,200)
No.
Thermocouple type
Range in
°
C Range
in
°
F
Binary (4-digit Hex)
4-digit BCD
Binary (4-digit Hex)
4-digit BCD
0
Pt100:
−
200.0 to 650.0
°
C
(
−
300.0 to 1,200.0
°
F)
F830 to FFFF to 1964
(
−
200.0 to
−
0.1 to 650.0)
F999 to 6500
(
−
99.9 to 650.0)
See note 3.
F448 to FFFF to 2EE0
(
−
300.0 to
−
0
.
1 to
1,200.0)
F999 to 9999
(
−
99.9 to 999.9)
See note 3.
1
JPt100:
−
200.0 to 650.0
°
C
(
−
300.0 to 1,200.0
°
F)
F830 to FFFF to 1964
(
−
200.0 to
−
0
.
1 to 650.0)
F999 to 6500
(
−
99.9 to 650.0)
See note 3.
F448 to FFFF to 2EE0
(
−
300.0 to
−
0
.
1 to
1,200.0)
F999 to 9999
(
−
99.9 to 999.9)
See note 3.
2 to
9
---
Settings 2 through 9 are not allowed.
Settings 2 through 9 are not allowed.
Содержание Sysmac CJ Series
Страница 1: ...OPERATION MANUAL Cat No W396 E1 03 SYSMAC CJ Series CJ1W TC Temperature Control Units...
Страница 2: ...CJ1W TC Temperature Control Units Operation Manual Revised December 2005...
Страница 3: ...iv...
Страница 5: ...vi...
Страница 13: ...xiv...
Страница 23: ......
Страница 93: ......
Страница 105: ......
Страница 107: ......
Страница 113: ......
Страница 115: ......