4
Introduction and Features
Section 1-1
ness in this design was that both responses could not be satisfied at the
same time.
1.
If the disturbance response were emphasized (i.e., P and I were re-
duced and D was increased), the SV response would oscillate and
overshoot.
2.
If the SV response were emphasized (i.e., P and I were increased and
D was reduced), the disturbance response would be delayed.
To overcome these problems, PID control with two degrees of freedom was
used for this Temperature Control Unit to take advantage of the strengths
of PID control and improve both disturbance and target response as shown
in 3, below.
■
Earlier PID Control Method
■
PID Control with Two Degrees of Freedom
■
Autotuning (AT) Function
The Temperature Control Unit is equipped with an autotuning (AT) function
that uses the “limit-cycle method” to calculate the optimum PID constant for
the controlled system. (The SV cannot be written for a loop if the loop is being
autotuned.)
1
2
The disturbance response is good, but
the SV response is delayed.
The SV response is good, but the
disturbance response is not.
3
Both the SV response and disturbance
response are good.
SV
AT starts.
AT stops.
Hunting period
Amplitude
Содержание Sysmac CJ Series
Страница 1: ...OPERATION MANUAL Cat No W396 E1 03 SYSMAC CJ Series CJ1W TC Temperature Control Units...
Страница 2: ...CJ1W TC Temperature Control Units Operation Manual Revised December 2005...
Страница 3: ...iv...
Страница 5: ...vi...
Страница 13: ...xiv...
Страница 23: ......
Страница 93: ......
Страница 105: ......
Страница 107: ......
Страница 113: ......
Страница 115: ......