13
Specifications
Section 2-1
Characteristics
Dimensions
31
×
90
×
65 mm (W
×
H
×
D)
Weight
150 g max.
Item
Specification
Item
Specification
Model number
CJ1W-TC00
@
CJ1W-TC10
@
Temperature sensor
Thermocouple: Types R, S, K, J, T, L, and B
Platinum resistance thermometer: Types Pt100
and JPt100
Number of loops
There are two types of Unit available: Four-loop Units and Two-loop Unit with heater burnout detec-
tion. (See note 1.)
Control output and
heater burnout alarm
output
NPN or PNP outputs, both with short-circuit protection (See note 1.)
Externally supplied power supply voltage: 24 VDC +10%/-15%
Maximum switching capacity: 100 mA (per output)
Leakage current: 0.3 mA max.
Residual voltage: 3 V max.
Temperature control
method
ON/OFF control or PID control with two degrees of freedom (Set with pin 6 on the Unit’s DIP
switch.)
Control operation
Forward or reverse operation (Set with pins 4 and 5 on the Unit’s DIP switch.)
RUN/STOP control
Supported (Controlled from the CPU Unit through bits allocated in the Special I/O Unit area.)
Operation with CPU
Unit in PROGRAM
mode
The Temperature Control Unit can be set to continue operating or stop operating when the CPU
Unit is in PROGRAM mode. (Set with pin 1 on the Unit’s DIP switch.)
Auto/Manual switch
for operational out-
put
None
Autotuning (AT) of
PID constant
Supported (Controlled from the CPU Unit through bits allocated in the Special I/O Unit area.)
Indication accuracy
Centigrade: ±0.3% PV or ±1
°
C (whichever is
larger) ± 1 digit max.
Farenheit: ±0.3% PV or ±2
°
F (whichever is
larger) ± 1 digit max.
• The accuracy will be ±2
°
C ± 1 digit max. when
using an L-type thermocouple or using a K or
T-type thermocouple below
−
100
°
C.
• The accuracy will be ±3
°
C ± 1 digit max. when
using an R or S-type thermocouple below
200
°
C.
• The B-type thermocouples may not be accu-
rate below 400
°
C. (See note 2.)
Centigrade: ±0.3% PV or ±0.8
°
C (whichever is
larger) ± 1 digit max.
Farenheit: ±0.3% PV or ±1.6
°
F (whichever is
larger) ± 1 digit max.
Sensitivity (when
using ON/OFF con-
trol)
0.0 to 999.9
°
C or
°
F (0.1
°
C or
°
F units)
Proportional band
0.1 to 999.9
°
C or
°
F (0.1
°
C or
°
F units)
Integral (reset) time
0 to 9,999 s (one-second units)
Derivative (rate) time 0 to 9,999 s (one-second units)
Control period
1 to 99 s (one-second units)
Sampling period
500 ms (4 loops)
Output refresh
period
500 ms (4 loops)
Display refresh
period
500 ms (4 loops)
Input compensation
value
−
99.9 to 999.9
°
C or
°
F (0.1
°
C or
°
F units)
Alarm output setting
range
−
999 to 9,999
°
C or
°
F (1
°
C or
°
F units)
The setting range will be
−
99.9 to 999.9
°
C or
°
F (0.1
°
C or
°
F units) when using a platinum resis-
tance thermometer or using a K or J-type thermocouple in decimal-point mode.
Содержание Sysmac CJ Series
Страница 1: ...OPERATION MANUAL Cat No W396 E1 03 SYSMAC CJ Series CJ1W TC Temperature Control Units...
Страница 2: ...CJ1W TC Temperature Control Units Operation Manual Revised December 2005...
Страница 3: ...iv...
Страница 5: ...vi...
Страница 13: ...xiv...
Страница 23: ......
Страница 93: ......
Страница 105: ......
Страница 107: ......
Страница 113: ......
Страница 115: ......