Troubleshooting
Section 5-2
5-2-2
Troubleshooting from Symptoms: Temperature Control Errors
Temperature Does Not Rise
Measured Temperature Higher than Control Temperature
Step
Possible Cause
Remedy
Connection
The measured temperature is incorrect.
Refer to
5-2-1 Troubleshooting from Symptoms: Mea-
surement Errors
for troubleshooting directions.
There is no load connected to the control output
terminals.
Connect a load.
The load’s polarity is reversed or the load is wired
to the wrong terminals.
Wire the load correctly.
The terminal screws are loose so there is poor
contact between the wires and terminals.
Tighten the terminal screws.
The heater’s power supply is not ON.
Turn ON the heater’s power supply.
The heater circuit is burned out or damaged.
Replace the heater with a good one.
The heater’s heat output is insufficient.
• Replace the heater with one that has a higher output.
• When using two or more heaters, check whether one
is burned out. Replace if necessary.
An overheating protection device is operating.
Increase the overheating protection device’s tempera-
ture setting so it is higher than the Temperature Control-
ler Unit’s set point.
Settings
The forward operation/reverse operation setting is
incorrect
Correct the setting.
The PID constant settings are not correct.
• Perform autotuning.
• Make the correct PID constant settings manually.
Temperature control has not been started.
Start temperature control.
A cooling fan is operating.
Turn OFF the cooling fan.
Step
Possible Cause
Remedy
Connection
The measured temperature is incorrect.
Refer to
5-2-1 Troubleshooting from Symptoms: Mea-
surement Errors
for troubleshooting directions.
The load is connected to the wrong control loop,
so the heater is being controlled by another loop’s
control output.
Wire the load correctly.
The contacts are fused in the relay operated by
the control output.
Replace the relay with a good one.
There is a short circuit in the relay operated by the
control output.
Replace the relay with a good one.
Current is flowing to the heater because of leak-
age current through the relay operated by the con-
trol output.
Connect a bleeder resistor to prevent operation due to
the leakage current.
Settings
The forward operation/reverse operation setting is
incorrect.
Correct the setting.
The PID constant settings are not correct.
• Perform autotuning.
• When autotuning is completed, refresh the PID con-
stants properly so that the Unit operates with the cal-
culated PID constants.
• Make the correct PID constant settings manually.
Usage
There is excessive overshooting.
Refer to
Excessive Overshooting or Undershooting
on
page 80 for troubleshooting directions.
Содержание Sysmac CJ Series
Страница 1: ...OPERATION MANUAL Cat No W396 E1 03 SYSMAC CJ Series CJ1W TC Temperature Control Units...
Страница 2: ...CJ1W TC Temperature Control Units Operation Manual Revised December 2005...
Страница 3: ...iv...
Страница 5: ...vi...
Страница 13: ...xiv...
Страница 23: ......
Страница 93: ......
Страница 105: ......
Страница 107: ......
Страница 113: ......
Страница 115: ......