54
Selecting the Control Operation (Forward/Reverse)
Section 3-4
3-4
Selecting the Control Operation (Forward/Reverse)
3-4-1
Forward (Cooling)/Reverse (Heating)
With forward operation (cooling), the manipulated variable is increased as the
PV increases. With reverse operation (heating), the manipulated variable is
increased as the PV decreases.
For example, when heating control is being performed and the present tem-
perature (PV) is lower than the set point (SP), the manipulated variable is
increased proportionally as the difference between the PV and SP increases.
Consequently, heating control uses “reverse operation” and cooling control
uses “forward operation.”
Set reverse operation or forward operation with pins 4 and 5 of the Unit’s DIP
switch. Pin 4 controls the operation of loops 1 and 3; pin 5 controls the opera-
tion of loops 2 and 4.
3-4-2
Setting the Control Operation (Pins 4 and 5)
Example Setting
If pin 4 is turned OFF and pin 5 is turned ON, loops 1 and 3 will be set for
reverse operation (heating) and loops 2 and 4 will be set for forward operation
(cooling).
The following diagram shows pins 4 and 5 set to their factory settings (OFF),
which sets reverse operation (heating) for all loops.
If this setting is changed during operation, the new setting will not become
effective until the power is turned ON or the Unit is restarted.
100%
0%
100%
0%
Low
temperature
SV
High
temperature
Forward operation
Low
temperature
SV
High
temperature
Reverse operation
Manipulated variable
Manipulated variable
123
45678
Pins 4 and 5
Control Operation
Reverse
Forward
Setting
OFF
ON
Содержание Sysmac CJ Series
Страница 1: ...OPERATION MANUAL Cat No W396 E1 03 SYSMAC CJ Series CJ1W TC Temperature Control Units...
Страница 2: ...CJ1W TC Temperature Control Units Operation Manual Revised December 2005...
Страница 3: ...iv...
Страница 5: ...vi...
Страница 13: ...xiv...
Страница 23: ......
Страница 93: ......
Страница 105: ......
Страница 107: ......
Страница 113: ......
Страница 115: ......