2-2
Section
Connecting H-PCF Cable Optical Ring System Cables
30
2-2-3 Installing Connectors
A special connector is used to connect the Optical Fiber Cable to the Controller
Link Support Board.
This manual does not provide details on Optical Fiber Cable preparation.
Connect the nodes in order beginning with the highest node in the network and
continuing on to lower nodes. When connecting a ring, also connect the end
node in the ring to the start node.
•
Always turn OFF the computer and backup power supply before connecting
Optical Fiber Cables or the backup power supply connector.
•
Special tools are required to attach Optical Fiber Cables to the connectors.
The cable may disconnect from the connector if the proper tools and methods
are not used during cable assembly.
Connection Procedure
1, 2, 3...
1. The Optical Fiber Cable’s power supply line is not used, so it can be cut.
2. As shown in the following diagram, secure the Optical Fiber Cable, and se-
cure the holding piece to the mounting bracket. Secure the two cables simul-
taneously for nodes (except the end nodes). Pay attention to the orientation
of the mounting bracket and the connector position when connecting the
cable from the highest node in the network to the rightmost connector (SL1),
and the cable from the next lower node to the leftmost connector (SL2).
Cable connects to
connector SL1
Cable connects to
connector SL2
3. Install the mounting bracket on the Board with the screws provided. Insert
the tip of the mounting bracket with the grooves into the hole on the Board
surface until it locks firmly (a), and then secure the other end of the mounting
bracket using the screw (b). Take care not to bend or pull the Optical Fiber
Cable forcefully.
(Cable is not shown for
clarity of the diagram.)
4. Remove the Optical Connector Cover from the Board again. If there are cov-
ers on the end connectors of the Optical Fiber Cable, remove them.
5. Double-check the direction of the cables. The cable from the node higher in
the network connects to the Board’s right connector and the cable to the
Содержание SYSMAC 3G8F7-CLK12-E
Страница 2: ......
Страница 4: ......
Страница 6: ......
Страница 10: ......
Страница 16: ......
Страница 30: ...1 2 Section Specifications and Configurations 14 1 2 5 Dimensions Wired Model 3G8F7 CLK21 E Unit mm ...
Страница 36: ......
Страница 56: ......
Страница 62: ......
Страница 78: ......
Страница 94: ......
Страница 128: ......
Страница 140: ......
Страница 158: ......