Section
9-3
Error Log
136
Error
code
Recorded
in
EEPROM
Correction
Detail code
Contents
Error
code
Recorded
in
EEPROM
Correction
2nd byte
1st byte
Contents
010D
Hex
Transmission failed; destination
address incorrect
Command block
Bits 0 to 7:
So rce node ddress
Check routing tables.
No
010E
Hex
Transmission failed; routing
tables not registered
Source node address
Bits 8 to 14:
Source Network
No
010F
Hex
Transmission failed; routing
table error
ource Network
address
Bit 15:
OFF
No
0110
Hex
Transmission failed; too many
relay points
OFF
Response block
Bits 0 to 7:
Destination node
ddress
Check routing tables and system
configuration. Do not try to access
Networks separated by more than
one other Network.
No
0111
Hex
Transmission failed; command
packet too long
address
Bits 8 to 14:
Destination Network
Be sure to use the correct FINS
command format.
No
0112
Hex
Transmission failed; header
error.
Destination Network
address
Bit 15:
ON
No
0113
Hex
I/O setting error; cannot send.
ON
(1st byte: bits 8 to 15;
2nd byte, bits 0 to 7)
Correct either the system
configuration or the registered I/O
tables.
No
0114
Hex
CPU bus error; cannot send.
Check the Board and cable
connections and clear the error.
No
0115
Hex
I/O duplication; cannot send.
Check the unit numbers to be
sure the same number is not set
twice in the same PC.
No
0116
Hex
CPU Bus Unit error; cannot
send.
Check the Board and cable
connections and clear the error.
No
0117
Hex
Internal buffer full
Increase number of retries or
reconfigure system to distribute
load.
No
0118
Hex
Illegal packet discarded
Check for nodes sending illegal
data.
Yes
0124
Hex
Maximum frame length
exceeded; cannot route.
Correct the FINS command
format. Also, be sure that the
parameters specified for the
command do not produce a
response that is too long.
No
0203
Hex
EEPROM error
01 Hex:
Read error
02: Hex:
Write error
01 Hex:
Data link
tables
02 Hex:
Network
parameters
03 Hex:
Routing
tables
Reset the relevant data. If the
error occurs again replace the
Controller Link Support Board.
Yes
0206
Hex
Number of participating nodes
decreased (local node still
participating)
Network
parameters
maximum
node
Number of
non-particip
ating nodes
Check network parameters, node
participation, cables, and
terminating resistance.
No
0207
Hex
Number of participating nodes
decreased (local node not
participating)
node
address
No
0208
Hex
polling node changed
Address of
previous
polling node
Address of
new polling
node
Check previous polling node.
No
0209
Hex
Network parameter
disagreement
00 Hex
Address of
polling node
Using the Controller Link Support
Software, check network
parameters.
Yes
Содержание SYSMAC 3G8F7-CLK12-E
Страница 2: ......
Страница 4: ......
Страница 6: ......
Страница 10: ......
Страница 16: ......
Страница 30: ...1 2 Section Specifications and Configurations 14 1 2 5 Dimensions Wired Model 3G8F7 CLK21 E Unit mm ...
Страница 36: ......
Страница 56: ......
Страница 62: ......
Страница 78: ......
Страница 94: ......
Страница 128: ......
Страница 140: ......
Страница 158: ......