6-4
Section
Response Codes
100
Main code
Remedy
Probable cause
Sub-
code
10: Command format
error
01
The command is longer than the max.
permissible length.
Check the command format of the
command and set it correctly.
02
The command is shorter than min.
permissible length.
Check the command format of the
command and set it correctly.
03
The designated number of data items
differs from the actual number.
Check the number of items and the data,
and make sure that they agree.
04
An incorrect command format has
been used.
Check the command format of the
command and set it correctly.
05
An incorrect header has been used.
(The source node’s relay table or relay
node’s local network table is wrong.)
Set the routing table correctly.
11: Parameter error
01
A correct memory area code has not
been used or Extended Data Memory
is not available.
Check the command’s memory area code
and set the appropriate code.
02
The access size specified in the
command is wrong, or the first
address is an odd number.
Set the correct access size for the
command.
03
The first address is in an inaccessible
area.
Set a first address that is in an accessible
area.
04
The end of specified word range
exceeds the acceptable range.
Check the acceptable limits of the data
area and set the word range within the
limits.
Check the data link tables to be sure the
limit to link words has not been exceeded.
06
A non-existent program no. has been
specified.
Check the program number and be sure
that it is set correctly.
09
The sizes of data items in the
command block are wrong.
Check the command data and be sure that
the sixes of the data items are correct.
co
d b oc
e
o g
Check the data link tables to be sure all
nodes in the refresh parameters are in the
common link parameters.
0A
The IOM break function cannot be
executed because it is already being
executed.
Either abort the current IOM break function
processing, or wait until it is completed and
execute the command.
Check the data link tables for node
addresses that have been set twice.
0B
The response block is longer than the
max. permissible length.
Check the command format and set the
number of items correctly.
0C
An incorrect parameter code has been
specified.
Check the command data and reenter it
correctly.
s ec ed
Check the data link table file for corruption.
Содержание SYSMAC 3G8F7-CLK12-E
Страница 2: ......
Страница 4: ......
Страница 6: ......
Страница 10: ......
Страница 16: ......
Страница 30: ...1 2 Section Specifications and Configurations 14 1 2 5 Dimensions Wired Model 3G8F7 CLK21 E Unit mm ...
Страница 36: ......
Страница 56: ......
Страница 62: ......
Страница 78: ......
Страница 94: ......
Страница 128: ......
Страница 140: ......
Страница 158: ......