3-1 Servo Driver Specifications
3-1-6 Control Input Details
Command Pulse Timing
Command Pulse Mode
Timing details
Feed pulse and direction signal
Maximum input frequency
Line driver: 750 kpps
Open collector: 187.5 kpps
t1, t2, and t3 > 3.0
µ
s
τ
≥
0.66
µ
s
T
≥
1.33
µ
s
(
τ
/ T)
×
100
≤
50 (%)
Reverse command
Forward command
Direction signal
Feed pulse
Reverse and forward pulses
Maximum input frequency
Line driver: 750 kpps
Open collector: 187.5 kpps
t2 > 3.0
µ
s
τ
≥
0.66
µ
s
T
≥
1.33
µ
s
(
τ
/ T)
×
100
≤
50 (%)
Forward command
Forward pulse
Reverse pulse
Deviation Counter Reset (ECRST)
The CN1 connector input pins are as follows:
+Deviation Counter Reset (8: +ECRST)
−
Deviation Counter Reset (9: –ECRST)
Functions
•
The value of the deviation counter will be reset when the deviation counter reset signal
turns ON and the position loop will be disabled.
•
Input the reset signal for 20 µs minimum. The counter will not be reset if the signal is
too short.
RUN Command Input (RUN)
RUN Command Input (pin 6: RUN)
Functions
This is the input that turns ON the power drive circuit for the main circuit of the Servo
Driver. If this signal is not input (i.e., servo-OFF status), the Servomotor cannot operate
except for JOG operations.
3-9
Содержание SMARTSTEP Junior R7D-ZP
Страница 3: ...2 ...
Страница 18: ...Section 1 Configuration Features and System ...
Страница 25: ...1 5 Applicable Standards 1 5 2 UL and cUL Standards 1 8 ...
Страница 26: ...Section 2 Dimensions Standard Models and ...
Страница 36: ...Section 3 Specifications ...
Страница 62: ...Section 4 System Design ...
Страница 86: ...Section 5 Operation ...
Страница 96: ...Section 6 Troubleshooting ...
Страница 109: ...6 5 Periodic Maintenance 6 5 3 Replacing the Cooling Fan 6 14 ...
Страница 110: ...Appendix ...