66
Special Settings and Communications Settings
Section 4-7
4-7
Special Settings and Communications Settings
The Startup Sequence Setting (UPS) will be displayed if the S8AS is in pro-
tection level 0 and the Up (SEL) Key (
) is pressed from the Over-Tempera-
ture Output Threshold Setting Display (TMP), which was described at the end
of
4-6 Shared Parameter Settings
.
Setting the Startup Sequence: UPS (Startup Sequence)
The startup sequence sets the startup sequence time for each branch output.
(The branch output that was most recently modified will be the current branch
output regardless of the operating mode.)
Note
The startup sequence sets a delay before the S8AS connects the branch out-
put after the power is turned ON. Connecting the branch outputs in sequence
instead of simultaneously can reduce the inrush current and reduce the load
on the power supply. For details on the startup sequence, refer to
2-5 Startup
Sequence Function
.
(Returns to UPS display.)
u p
s
u p
s
*
0
#
8
1
2
3 4 5
6
V A Yrs
s
°
C
1
2
3 4 5
6
V A Yrs
s
°
C
1
2
3 4 5
6
V A Yrs
s
°
C
1
2
3 4 5
6
V A Yrs
s
°
C
(To change the
branch output)
Press the
Key to display the startup sequence time
set value (SV) for the current branch output. The SV can
be changed by pressing the
and
Keys. The set-
ting range is 0.0 to 99.9 s (0.1-s increments).
Note
If the
or
Key is pressed for more than 2 s,
the SV will change in 1.0-s increments instead of
0.1-s increments.
Change the SV with the
and
Keys.
The S8AS will automatically return to the UPS display if no
key is pressed within 3 s.
When the
Key is pressed, the SV display will flash.
When the flashing stops, the new setting will be saved and
the S8AS will return to UPS display.
If you want to confirm the new setting, press the
Key
again from the UPS display.
To change the startup sequence settings of other branch
outputs, press the
Key from the UPS display to select
the desired branch output, and then follow the procedure to
change the settings.
Switch to the
Shutdown
Sequence
setting.
Содержание S8AS
Страница 1: ...S8AS Smart Power Supply USER S MANUAL Cat No Z269 E1 05...
Страница 2: ......
Страница 3: ...S8AS Smart Power Supply User s Manual Revised September 2013...
Страница 4: ...iv...
Страница 6: ...vi...
Страница 104: ...86 Run Mode Section 5 4...
Страница 128: ...110 ASCII List Section 6 10 6 10 ASCII List Even parity...
Страница 144: ...126 Revision History...
Страница 145: ......