![Omron S8AS Скачать руководство пользователя страница 132](http://html1.mh-extra.com/html/omron/s8as/s8as_user-manual_743691132.webp)
114
Seven-segment Error Codes
Section 7-2
7-2
Seven-segment Error Codes
Error Display List
• When two or more errors occur simultaneously, the higher priority error
(higher in the table above) will be displayed.
Seven-segment
display
Error
code
Meaning
Probable cause and remedy
erp
ERP
Memory error on
power supply side
These are S8AS system errors.
When one of these error codes is displayed, check the system config-
uration and clear the error, and then turn the power supply OFF and
ON again.
If the error code persists, contact your OMRON representative
regarding the error.
.
---
S8AS hardware error
alp
ALP
Power supply voltage
error
e98
E98
RAM error
e97
E97
EEPROM read error
e96
E96
EEPROM write error
e95
E95
Internal communica-
tions error
e94
E94
Short circuit failure
e00
E00
EEPROM initialization
error
e01
E01
EEPROM error
e02
E02
Model error
e03
E03
Factory default detec-
tion mode
e10
E10
Data other than com-
munications data is
corrupted.
There is an error in the parameter
settings.
Press the Mode Key to switch to
the parameter initialization dis-
play. After initializing the parame-
ters, set them again.
This error is treated as a system
error for the S8AS-24006N/
48008N.
a10
A10
Abnormal voltage trip-
ping
The power supply voltage
exceeded 28.8 V.
Check the power supply voltage.
a11
A11
Abnormal current trip-
ping
The branch output's current
exceeded the current tripping
threshold.
Check whether the connected
device is correct and check
whether the set value is appropri-
ate.
a12
A12
Total current tripping
All branch outputs were cutoff
because the total current and the
power-ON time exceeded the
abnormal total current tripping
conditions.
Check whether the connected
devices are suitable and operat-
ing within the total current limit.
a21
A21
Undervoltage alarm
The output voltage dropped
below the undervoltage detection
threshold.
Check the power supply voltage
and the set value.
a23
A23
Maintenance forecast
monitor output
The replacement time calculated
by the S8AS is lower than the
notification time.
Indicates that the replacement
time is approaching.
a23
/
hot
A23/
HOT
Overheating alarm
The S8AS is overheated
Take steps to reduce the internal
temperature.
a30
A30
Over-temperature out-
put
The S8AS's internal temperature
exceeded the over-temperature
output threshold.
Check for a high ambient temper-
ature and check the setting of the
over-temperature output thresh-
old.
Take steps to reduce the temper-
ature in the control panel.
Содержание S8AS
Страница 1: ...S8AS Smart Power Supply USER S MANUAL Cat No Z269 E1 05...
Страница 2: ......
Страница 3: ...S8AS Smart Power Supply User s Manual Revised September 2013...
Страница 4: ...iv...
Страница 6: ...vi...
Страница 104: ...86 Run Mode Section 5 4...
Страница 128: ...110 ASCII List Section 6 10 6 10 ASCII List Even parity...
Страница 144: ...126 Revision History...
Страница 145: ......