90
Frame Structure
Section 6-2
6-2
Frame Structure
6-2-1
Command Frame Structure
STX
This code, 02 hex, indicates the beginning of a communica-
tions frame (text). This code must always be set as the first
byte.
When another STX code is received during reception, the
reception starts again from the point where the STX was
received.
Node No.
(Node address)
• The node address identifies the destination node.
• The node address can be set to 00 to 32.
• There will be no response to a transmission with an invalid
node address.
Subaddress
The subaddress is not used in the S8AS. Always set the sub-
address to “00.”
SID (Service ID)
The SID is not used in the S8AS. Always set the SID to “0.”
FINS-mini
command text
The command and required text are placed here. Refer to
6-2-
3 FINS-mini Structure
for details.
ETX
This code, 03 hex, indicates the end of text.
BCC
This is the block check character.
The BCC is calculated by taking the exclusive OR of all bytes
from the node number to the ETX.
S T X
0 1 0 0 0
E T X
1 2
2 1
1
1
Text
Node No.
Subaddress
FINS-mini command text
BCC calculation range
BCC
SID
Содержание S8AS
Страница 1: ...S8AS Smart Power Supply USER S MANUAL Cat No Z269 E1 05...
Страница 2: ......
Страница 3: ...S8AS Smart Power Supply User s Manual Revised September 2013...
Страница 4: ...iv...
Страница 6: ...vi...
Страница 104: ...86 Run Mode Section 5 4...
Страница 128: ...110 ASCII List Section 6 10 6 10 ASCII List Even parity...
Страница 144: ...126 Revision History...
Страница 145: ......