32
Basic Function Details
Section 2-4
Current Tripping Characteristics
■
Standard Detection
■
Instantaneous Detection
■
Extended Detection
Note
The S8AS contains a current-restricting circuit that prevents a cur-
rent above a specific value from flowing. The current is thus restrict-
ed during the time required to cut off the output.
Note
After sampling and converting each branch output's current every 1 ms, the
S8AS processes the values in the CPU and controls the branch output cut-
offs. This method achieves high-speed, high-accuracy tripping. In addition, to
minimize the effects of excessive currents caused by short-circuits, the S8AS
is equipped with built-in current-limiting circuits. Consequently, there is a
Setting
range
Tripping region
Current-
limiting
by internal
circuits
Current (A)
100
Time (ms)
60
20
0.5
3.8
11
16
19
Tolerance of current trip-
ping alarm threshold:
±
0.3 A. When the trip-
ping current (0.5 to
3.8 A) is detected, it is
cut off within 100 ms.
20
0.5
3.8
19
Setting
range
Tripping region
Current-
limiting
by internal
circuits
Current (A)
Time (ms)
Tolerance of current trip-
ping alarm threshold:
±
0.3 A. When the trip-
ping current (0.5 to
3.8 A) is detected, it is
cut off within 20 ms.
20
0.5
3.8
19
60
1,000
11
16
Setting
range
Tripping region
Current-
limiting
by internal
circuits
Current (A)
Time (ms)
Tolerance of current trip-
ping alarm threshold:
±
0.3 A.When the trip-
ping current (0.5 to
3.8 A) is detected, it is
cut off within 1,000 ms.
Содержание S8AS
Страница 1: ...S8AS Smart Power Supply USER S MANUAL Cat No Z269 E1 05...
Страница 2: ......
Страница 3: ...S8AS Smart Power Supply User s Manual Revised September 2013...
Страница 4: ...iv...
Страница 6: ...vi...
Страница 104: ...86 Run Mode Section 5 4...
Страница 128: ...110 ASCII List Section 6 10 6 10 ASCII List Even parity...
Страница 144: ...126 Revision History...
Страница 145: ......