27
Specifications
Section 2-3
Note
(1) Do not use an inverter output for the Power Supply. Inverters with an out-
put frequency of 50/60 Hz are available, but the rise in the internal tem-
perature of the Power Supply may result in ignition or burning.
(2) Refer to
Derating Curve
on page xiv for details.
(3) If the output voltage adjuster (V. ADJ) is turned, the voltage will increase
by more than 10% of the voltage adjustment range. When adjusting the
output voltage, confirm the actual output voltage from the Power Supply
and be sure that the load is not damaged. If the output voltage exceeds
28.8 V, all branch outputs will be cut off.
(4) Rated input and output conditions: Rated input voltage, rated frequency,
rated output voltage, rated total output current, and maximum cutoff out-
put current.
(5) 100% load conditions: Rated output voltage, rated total output current,
and maximum cutoff output current.
Others
Ambient operating tempera-
ture
Refer to the derating curve (no icing or condensation). (See note 2.)
Storage temperature
−
25 5o 65
°
C
Ambient operating humidity
25% to 85% (storage: 25% to 90%)
Withstand voltage
3.0 kVAC for 1 min between all input terminals collectively and all branch output,
all I/O signal, and all communications terminals collectively (detection current:
20 mA)
2.0 kVAC for 1 min between all inputs and protective earth (Detection current:
20 mA)
1.0 kVAC for 1 min between protective earth and all branch output, all I/O signal,
and all communications terminals collectively (Detection current: 30 mA)
500 VAC for 1 min between all branch output and all I/O signal/communications
terminals collectively (Detection current: 20 mA)
500 VAC for 1 min between all I/O signal terminals collectively and communica-
tions terminals collectively (Detection current: 20 mA)
500 VAC for 1 min between all I/O signal terminals collectively and all output sig-
nal terminals collectively (detection current: 20 mA)
Insulation resistance
100 M
Ω
min. at 500 VDC between the protective earth terminal or all input termi-
nals collectively and all branch output, all I/O signal, and all communications ter-
minals collectively
Vibration resistance
No abnormality after 10 to 55 Hz at 0.375-mm single amplitude for 2 h each in 3
directions.
Shock resistance
No abnormality after 150 m/s
2
3 times each in 6 directions.
Output indicator
Provided (Color: green)
Conducted EMI
Conforms to EN 61204-3 Class A and FCC Class A.
Radiated EMI
Conforms to EN 61204-3 Class A.
Safety standards
cULus: UL508 (Listing. Class2: Per UL1310), CSA C22.2 No.107.1 (Class2: Per
CSA C22.2 No.223)
cURus: UL60950-1, CSA C22.2 No.60950-1
EN: EN50178, EN60950-1
VDE: VDE0160, VDE0805 Teil1
Weight
2,400 g max.
Item
Model
S8AS-48008
S8AS-48008N
S8AS-48008R
Содержание S8AS
Страница 1: ...S8AS Smart Power Supply USER S MANUAL Cat No Z269 E1 05...
Страница 2: ......
Страница 3: ...S8AS Smart Power Supply User s Manual Revised September 2013...
Страница 4: ...iv...
Страница 6: ...vi...
Страница 104: ...86 Run Mode Section 5 4...
Страница 128: ...110 ASCII List Section 6 10 6 10 ASCII List Even parity...
Страница 144: ...126 Revision History...
Страница 145: ......