23
Specifications
Section 2-3
Func-
tions
Over-temper-
ature detec-
tion function
Over-tempera-
ture
Setting range: 25 to 90
°
C
(in 1
°
C increments)
90
°
C (Cannot be
changed.)
Setting range: 25 to 90
°
C
(in 1
°
C increments)
Over-tempera-
ture output
Photoswitch output
30 VDC max. and 50 mA max., Leakage current: 0.1 mA max.,
Residual voltage: 2 V max.
Display func-
tions
Output voltage
display
Display range: 17.0 to 30.0 V
Display accuracy: 2% rdg
±
1 digit max.
Output current
display
Branch output display range: 0.0 to 4.0 A
Peak output current display range: 0.0 to 20.0 A
Total current display range: 0.0 to 40.0 A
Display accuracy: 5% FS (4 A)
±
1 digit max.
Maintenance
forecast moni-
tor display
Display range: FUL (Full)/HLF (Half)/0.0 to 5.0 yr
Temperature
display
Display range:
−
20 to 100
°
C
Display accuracy: 2
°
C
±
1 digit max.
External Tripping Input
The input can be enabled
or disabled for each
branch output.
19.2 to 30 VDC, mini-
mum signal width: 10 ms,
tripping after input within
20 ms + the shutdown
sequence set time
All branch outputs:
Enabled (Cannot be
changed.)
19.2 to 30 VDC, mini-
mum signal width: 10 ms,
tripping after input within
20 ms + the shutdown
sequence set time
The input can be enabled
or disabled for each
branch output.
19.2 to 30 VDC, mini-
mum signal width: 10 ms,
tripping after input within
20 ms + the shutdown
sequence set time
Startup sequence
Setting range: 0.0 to
99.9 s in 0.1-s incre-
ments
Branch output 1: 0.0 s
(Cannot be changed.)
Branch output 2: 0.4 s
(Cannot be changed.)
Branch output 3: 0.8 s
(Cannot be changed.)
Branch output 4: 1.2 s
(Cannot be changed.)
Branch output 5: 1.6 s
(Cannot be changed.)
Branch output 6: 2.0 s
(Cannot be changed.)
Setting range: 0.0 to
99.9 s in 0.1-s incre-
ments
Shutdown sequence
Setting range: 0.0 to
99.9 s in 0.1-s incre-
ments
All branch outputs:
0.0 s (Cannot be
changed.)
Setting range: 0.0 to
99.9 s in 0.1-s incre-
ments
Communications
Not supported
Supported (RS-485)
Sampling period
1 ms
Parallel connection
Not supported.
Series connection
Not supported.
Item
Model
S8AS-24006
S8AS-24006N
S8AS-24006R
Содержание S8AS
Страница 1: ...S8AS Smart Power Supply USER S MANUAL Cat No Z269 E1 05...
Страница 2: ......
Страница 3: ...S8AS Smart Power Supply User s Manual Revised September 2013...
Страница 4: ...iv...
Страница 6: ...vi...
Страница 104: ...86 Run Mode Section 5 4...
Страница 128: ...110 ASCII List Section 6 10 6 10 ASCII List Even parity...
Страница 144: ...126 Revision History...
Страница 145: ......