56
References
AC input
AC output
Reference
A. Specifications
Rated input voltage
Voltage range
Rated frequency
Maximum current
Number of phases
Input plug type
Input protection
Input protection capacity
Output capacity
Output waveform
(In Commercial Power Mode/
Batttery Mode)
Rated voltage
Output voltage
(reference value)
(In Commercial Power Mode)
Output voltage
(In Battery mode)
Frequency
Number of phases
Switching time
Waveform distortion rate
Operation method
Cooling method
Line interactive method
Forced air cooling
100 VAC
90 VAC+3% ~ 118 VAC+3% (100 VAC output/normal voltage sensitivity)
85 VAC+3% ~ 118 VAC+3% (100 VAC output/low voltage sensitivity)
92 VAC+3% ~ 118 VAC+3% (115 VAC output/normal voltage sensitivity)
88 VAC+3% ~ 118 VAC+3% (115 VAC output/low voltage sensitivity)
50 / 60Hz+4Hz
13A (BN100XR)
18A (BN150XR)
24A (BN240XR)
Single phase two lines
3-pin (with ground)
NEMA 5-15P (BN100XR)
NEMA 5-15P (replaceable with L5-20P) (BN150XR)
NEMA L5-30P (BN240XR)
Reset-type overcurrent protection device (BN100XR/BN150XR)
Fuse (built-in) (BN240XR)
15A (BN100XR)
20A (BN150XR)
30A (BN240XR)
(BN100XR)
1000VA/700W
(BN150XR)
1500VA (1110VA)/1000W (100 VAC output/normal voltage sensitivity)
1420VA (1035VA)/1000W (100 VAC output/low voltage sensitivity)
1500VA (1140VA)/1000W (115 VAC output/normal voltage sensitivity)
1480VA (1080VA)/1000W (115 VAC output/low voltage sensitivity)
Data in parentheses (
) are for when 15A input plug is used
(BN240XR)
2310VA/2000W (100 VAC output/normal voltage sensitivity)
2160VA/2000W (100 VAC output/low voltage sensitivity)
2370VA/2000W (115 VAC output/normal voltage sensitivity)
2250VA/2000W (115 VAC output/low voltage sensitivity)
Sine wave / Shine wave
100 VAC /115 VAC
90 VAC ~ 110V (100 VAC output/normal voltage sensitivity)
90 VAC ~ 110V (100 VAC output/low voltage sensitivity)
100 VAC ~ 125V (115 VAC output/normal voltage sensitivity)
95 VAC ~ 125V (115 VAC output/low voltage sensitivity)
100 VAC+ 10%/115 VAC+ 10%
Same as input frequency
50 / 60Hz+0.1Hz (in Battery mode)
Single phase two lines
10 ms or less
22% or less (in Battery mode, under rectifying load, at rated output)
[*The total load capacity to
connect the UPS should
be less than rated value
for both the VA value and
the Watt value.]