46
6. Using the UPS monitoring software
The USB and RS-232C ports cannot be used simultaneously.
●
The UPS monitoring software and can be used with either the USB or RS-232C ports of the UPS, but they
both cannot be used at the same time.
Starting operation during scheduled shutdown with UPS monitoring software
●
If the UPS operation is started during the scheduled shutdown period, turn OFF the power switch, and
then turn it ON again.
The UPS can be restarted manually.
In this case, the next set scheduled ON operation is cancelled.
Using UPS service of Windows NT
●
If you are using Windows NT Server, make the settings using the server menu as shown below. An
incorrect setting of the remote UPS shutdown the UPS will be unable to perform backup in the event of a
power failure.
For more detailed information, refer to the Windows NT 4.0 manual or the Windows NT 4.0 help file.
The signal settings are as follows:
Power supply shutdown signal: Negative (for initial value, Windows NT server is set as negative, and
OS2Lan server is set as positive)
Battery weak/dead signal:
Negative (for initial value, Windows NT server is set as negative, and
OS2Lan server is set as negative)
Remote UPS shutdown:
Positive (for initial value, Windows NT server is set as negative, and
OS2Lan server is set as negative)
●
For Netware users, call up the command input screen, and enter the following to load a UPS module into
the file server.
LOAD UPS TYPE=6 PORT=__ REV=2
After this is input, press the Enter key.
In the command line, after "PORT=", enter the number of the serial port that is connected to the UPS. (1 or
2)
Explanations
6-3 About the included UPS monitoring software
The included UPS monitoring software enables you to save files automatically and perform shutdown processing
of the computer when there is a power failure. However, the time between the occurrence of a power failure
and the completion of the shutdown of your PC must be within the backup time measured in "4-1 Measuring
method of the backup time" on page 36. For more detailed explanations and operations, refer to either the UPS
monitoring software instruction manual or the online help for the UPS monitoring software.
When using the included UPS monitoring software, it is possible to change the UPS operation mode settings,
use additional functions, perform scheduled operation, and conduct redundant operation by connecting multiple
UPS to servers with redundant power supply, etc.