3. Operating the UPS
C. Failure (displays and beeps when a failure occurs in a device)
Status:
The UPS stops due to a failure of the internal
circuit of the UPS, an output short, or
abnormal internal temperature.
Remedy:
●
Turn off the UPS and devices connected to
the UPS. Disconnect all devices connected
to the UPS and press the Power switch again.
In a case where the status of A-3 on page 33
occurs, there may be a malfunction in a
device connected to the UPS. Check the
devices.
●
If the same display appears after taking the
above countermeasures, stop the UPS for
approximately 1 hour and then press the
Power switch again.
In the case when the status of A-3 on page
33 occurs, the temperature inside the UPS
must have increased. Check whether ambient
temperature is below 40
°
C and make sure
that a vent has not become obstructed.
◆
If the trouble still remains despite performing
the above checks, there has likely been a
failure of the internal circuit.
Contact the dealer or our Repair Center.
1
Continuous Stop
Stop
No.
Display
Beep Output Charge
Description
B. Failure (displays and beeps when a power failure and/or irregularities
in the input power supply occur)
Continuous
Every
4 seconds
ON
Stop
(dis-
charging)
Status:
Due to power failure or input voltage
irregularities, power is being supplied to
devices connected to the UPS in the battery
mode. The amount of charge remaining is
displayed on the level meter.
Remedy:
To prevent battery depletion, turn off the
devices linked to the UPS after shutting them
down.
Status:
Power is being supplied to devices
connected to the UPS in battery mode.
The remaining charge is nearly exhausted,
so the output will stop soon.
The remaining charge is displayed on the
level meter.
Remedy:
To prevent battery depletion, turn off the
devices linked to the UPS after shutting them
down.
Continuous
Every 1
second
ON
Stop
(dis-
charging)
1
2
No.
Display
Beep Output Charge
Description
AC115V
OUTPUT
B
25% 50% 75% 100%
C
Lit
Lit
<High battery capacity>
Not lit
Blinking
Lit or not lit,
depending on status
AC115V
OUTPUT
B
25% 50% 75% 100%
C
Lit
<Low battery capacity>
Not lit
Blinking
Lit or not lit,
depending on status
AC115V
OUTPUT
B
25% 50% 75% 100%
C
Lit
Lit
Not lit
Blinking
Lit or not lit,
depending on status