52
9. Additional functions and function setting changes for the UPS
9-2 Estimated backup time and backup time test in
Battery mode
1. Estimated backup time
The estimated time of backup in the current operating conditions is displayed on the UPS monitoring
software monitor screen.
•
In Line mode: Estimated backup time under the current charge status and load conditions is displayed.
•
In Battery mode: Estimated backup time is displayed. An accurate estimate of backup time cannot be
performed. Use this as a rough estimate.
2. Backup time adjustment
As the battery deteriorates, backup time becomes shorter. To estimate backup time, the decrease of battery
capacity needs to be measured.
•
Periodically and voluntarily perform backup operation, and measure and adjust for the battery capacity.
•
During backup time adjustment, the battery indicator blinks once per second. There is no beeping sound.
•
Scheduled backup time adjustment can be performed by setting the schedule in the UPS monitoring
software.
For example, set the schedule for once every six months as a guide.
•
Voluntary backup time adjustment can also be performed by using the UPS monitoring software.
9-3 UPS functions whose settings can be changed
from the UPS monitoring software
These setting details can be selected and input from the included UPS monitoring software, and the settings
are maintained in the event that power supply is cut.
•
They cannot be used with UPS services included in the OS.
1. Beep ON/OFF setting
(Factory setting)
Beep ON
O N : When the alarm is necessary, a beep will sound.
OFF : This setting disables the beep sound.
When an input power supply abnormality (power failure, input overvoltage) activates Battery mode,
there is no beep sound. It is not possible to disable the beeps that accompany other alarms.
2. Auto battery test ON/OFF
(Factory setting)
Auto battery test ON
O N : Battery tests are performed automatically.
If the result of the battery test indicates that the battery needs to be replaced, the battery deterioration
alarm will sound.
OFF : The auto battery test is disabled.
Turn this setting OFF when you do not want to check the battery automatically and run Battery mode.
3. Auto restart ON/OFF
(Factory setting) Auto restart ON
O N : The UPS restarts automatically and begins output when commercial power is restored after a power
failure that shut down the UPS.
OFF : After the UPS is shut down, it does not automatically restart when commercial power is restored.
The UPS can be restarted only by pressing the power switch.