33
3. Operating the UPS
3-3 Beeps and displays
A. Normal (Normal operation status)
Status:
Operation is interrupted due to removal of
the AC Input Plug or abnormal input power
supply.
1
2
None
None
Stop
Stop
Stop
ON
The AC Input Plug is inserted, and the input
power supply is normal. Operation is stopped.
Power switch : OFF
Charging
No.
Display
Beep Output Charge
Description
Status:
The AC Input Plug is inserted, and the input
power supply is normal, and in operation.
The remaining capacity and charging status
is indicated on the level meter.
Power switch : ON
Charging status and load capacity is
displayed.
3
None
ON
ON
AC115V
OUTPUT
B
25% 50% 75% 100%
C
Lit
Not lit
Blinking
Lit or not lit,
depending on status
AC115V
OUTPUT
B
25% 50% 75% 100%
C
Lit
Blinks once every 10 seconds
Not lit
Blinking
Lit or not lit,
depending on status
AC115V
OUTPUT
B
25% 50% 75% 100%
C
Lit
Not lit
Blinking
Lit or not lit,
depending on status
<Input current over 15A>
Status:
Input current is over 15A.
Remedy:
Replace with a 20A type plug.
OR
Reduce the connected capacity until the
"Input over 15A" indication disappears.
4
None
ON
ON
AC115V
OUTPUT
B
25% 50% 75% 100%
C
Lit
Not lit
Blinking
Lit or not lit,
depending on status
<Input current over 15A>
BN150XR only