![Omron POWLI BN100XR Скачать руководство пользователя страница 28](http://html.mh-extra.com/html/omron/powli-bn100xr/powli-bn100xr_instruction-manual_744596028.webp)
26
2. Installation and connection
INPUT AC100V
50/60Hz 30A MAX.
34Z5
U.P.S.
SER.
MODEL : BN240XR
無停電電源装置
BATTERY CONNECTOR
Volt : 72Vdc
XX A
20A MAX.
A
20A MAX.
B
15A MAX.
C
USB
RS232C
TO BATTERY
CABINET
OUTPUT
AC100-115V
50/60Hz
24A/2000W MAX.
C
B
A
Output receptacle A
Output receptacle B
Output receptacle C
●
Connecting devices to the output receptacles
BN100XR
BN150XR
BN240XR
It is not p
ossible to connect a device that surpasses the rated capacity of the output recep-
tacle, even if it is within the output rated capacity of the BN240XR. Distribute the connec-
tions so that each outlet is within its rated capacity.
Make sure that the total capacity of the devices connected to the output receptacle does not
exceed the output rated capacity of the BN100XR/BN150XR/BN240XR. If the overload indi-
cation (
) is displayed, reduce the number of connected devices.
Output receptacle group
Outlet rated capacity
Quantity
Output receptacle A
20A
2
Output receptacle B
20A
2
Output receptacle C
15A
2
Output receptacle group
Outlet rated capacity
Quantity
Output receptacle A
15A
2
Output receptacle B
15A
1
Output receptacle C
15A
1
INPUT AC100V
50/60Hz 15A MAX.
INPUT AC100V
50/60Hz 15A MAX.
INPUT PROTECTION
15A
RS232C
USB
SER. :
1
OUTPUT
AC100-115V
50/60Hz
15A/1000W MAX.
1
34Z5
U.P.S.
MODEL : BN150XR
A
B
C
Output receptacle A
Output receptacle B
Output receptacle C
Output receptacle group
Outlet rated capacity
Quantity
Output receptacle A
10A
2
Output receptacle B
10A
1
Output receptacle C
10A
1
INPUT AC100V
50/60Hz 15A MAX.
INPUT AC100V
50/60Hz 15A MAX.
INPUT PROTECTION
15A
RS232C
USB
SER. :
1
OUTPUT
AC100-115V
50/60Hz
15A/1000W MAX.
1
34Z5
U.P.S.
MODEL : BN150XR
A
B
C
Output receptacle A
Output receptacle B
Output receptacle C