27
2. Installation and connection
●
When the overload indication appears, output stops
The time it takes until output stoppage occurs differs depending on the degree of overload.
●
The rated output capacity differs according to the voltage setting mode.
Operation status
Overload amount
Time until output stops
Line mode
Around 110% and up
5 minutes
Around 120% and up
10 seconds
Battery mode
Around 115% and up
30 seconds
Around 125% and up
Immediately
Output capacity of BN150XR
AC100V output / normal voltage sensitivity
1500VA/1000W
AC100V output / low voltage sensitivity
1420VA/1000W
AC115V output / normal voltage sensitivity
1500VA/1000W
AC115V output / low voltage sensitivity
1480VA/1000W
When using input plug 15A
1000VA/900W
For information on "Voltage selection mode", see "9-3 UPS functions whose settings can be changed from
the UPS monitoring software" on pages 52 - 53.
Output capacity of BN240XR
AC100V output / normal voltage sensitivity
2310VA/2000W
AC100V output / low voltage sensitivity
2160VA/2000W
AC100V output / normal voltage sensitivity
2370VA/2000W
AC100V output / low voltage sensitivity
2250VA/2000W
Note that even when using a 15A plug, the maximum output at which the overload indication appears
does not change.
If the "Input over 15A" indication (blinking
) appears, replace with a 20A plug.
Output capacity of BN100XR
AC100V output / normal voltage sensitivity
1000VA/700W
AC100V output / low voltage sensitivity
1000VA/700W
AC115V output / normal voltage sensitivity
1000VA/700W
AC115V output / low voltage sensitivity
1000VA/700W
When using input plug 15A
1000VA/900W