KP100G
12
Conditions for Disconnecting from the Grid
Grid Voltage
When the grid voltage varies from the ranges listed in Table 3-1, the KP100G disconnects from the grid.
Table 3-1 Conditions UV/OV of the KP100G
Model
Country
UV (AC Undervoltage)
OV (AC Overvoltage)
KP100G-OD-ES Spain
196VAC
253
VAC
KP100G-OD-IT
Italy
191 VAC
264 VAC
253 VAC within 10min (See Note)
KP100G-OD-DE
Germany
196 VAC
264 VAC within 0.2sec (See Note)
Note: According to VDE0126-1-1 4.2.2, when grid voltage exceeds 115%UN, the KP100G must disconnect from grid within 0.2sec.
According to VDE0126-1-1 4.2.3, the KP100G monitor grid voltage in 10min interval, and when grid voltage exceeds
100%UN in 10min, the KP100G disconnect from grid.
Grid Frequency
When the grid frequency varies from the ranges listed in Table 3-2, the KP100G disconnects from the grid.
Table 3-2 Conditions UF/OF of the KP100G
Country Setting
UF (Under frequency )
OF (Over frequency)
KP100G-OD-ES
Spain
49.0 Hz
51.0 Hz
KP100G-OD-IT
Italy
49.7 Hz
50.3 Hz
KP100G-OD-DE Germany
47.5 Hz
50.2 Hz
ENS standards require that each model be tested by a third-party verification institute, and that all ENS units be tested prior to shipping.
To ensure
that switching devices (relays) operate properly, always do an operational check before starting up the KP100G. If the test results are negative, the
KP100G will repeat the self-diagnostics. If the problem remains, it will be necessary to have a specialist diagnose it. Malfunctions are indicated by the
LCD.
Содержание KP100G
Страница 1: ...KP100G Technical manual Grid Connect Photovoltaic Inverter Part number 1868180 8 A...
Страница 50: ...KP100G 50 EC DECLARATION OF CONFORMITY...
Страница 51: ...KP100G 51 Technical Report...
Страница 52: ...KP100G 52 Declaration of Conformity RD1663 2000...
Страница 53: ...KP100G 53 Declaration of Conformity DK5940...