KP100G 

 

Important installer information: 

 

WARNING 

 

 

CAUTION 

 

Injury due to electric shock, or fire, may possibly 
occur. Do not open the front cover or disassemble, 
modify, or repair. 

 

Burn injury will occur. Do not touch the upper part 
of the product cabinet during operation or 
immediately after stopping operation. 

Functional impairment may possibly occur due to 
the destruction or damage of internal components 
caused by condensation. Do not install in places 
subject to high humidity, steam, or high 
temperatures. 

Fire will occur. Do not obstruct ventilation holes or 
place any objects within 20 cm of the ventilation 
holes. 

Significant injury may possibly occur due to fire. 
Do not use the product in a flammable gas 
atmosphere (including flammable sprays such as 
pesticides). 

Damage from burning will occur. Turn OFF the AC 
breaker before removing the MC connector. Do not 
connect or disconnect the MC connector while the 
current is flowing.  

 

Injury or functional impairment may possibly 
occur due to electric shock or burns. Do not install 
in places that are within the reach of children. 

Injury may occasionally occur. 
Be careful by two persons when for transporting 
and placing in position. 

Fire will occur. Do not install near highly 
combustible items or heat sources (stoves, heaters, 
boilers, etc.). 

Confirm the polarity of the cable from the PV 
module and the AC side to ensure correct 
connection and avoid possible damages which are 
not covered by warranty. This can be done with a 
standard Multimeter. 

Significant property damage may occasionally 
occur. Do not use the product at any country other 
than the designated one. 

 

Injury will occur due to the product falling. Install 
the product in a location that will be able to support 
its weight (35 kg). The installation location must be 
able to withstand the force of 185 N

m of torque at 

each mounting screw. 

Injury or electric shock will occur. Read the 
manual and follow prior to installing or performing 
maintenance on the product, and follow the 
instructions carefully. 

Injury will occur due to the product falling. Use the 
installation parts and materials that are included 
with the product. 

Have the installation done by a person with 
qualifications approved by the relevant local utility.  

 

IP65 performance may not be provided, if you 
don’t follow these instructions:  

1. Tighten the cable glands of AC output and RS-
485. 

 

Injury due to electric shock or property damage due 
to burning may occasionally occur. Mount the 
enclosed caps onto MC connector that is not used. 
Mount the rubber bushing with no hole in RS-485 
connector if RS-485 is not used. Tighten the screw of 
RS-232C protection cover properly if RS-232C is 
not used. 

 

2. Use a wire with a cross-sectional area of 4 mm

2

 

or AWG12 and a cable with diameter of 6 mm is 
allowed for the AC connector. Use a wire with a 
cross-sectional area of 10 mm

2

 or AWG8 is a cable 

with diameter of 7.5 to 15 mm allowed for GND 
connector. 

 

 

3. Tighten the screws of the AC output over and RS-
232C and RS-485 protection cover to the specified 
torque (1.3 to 1.6 N

m). Or tighten the screws of RS-

232C connecter properly. 
4. Some thinning of the cable may be caused due to 
usage conditions, with the result that IP65 
performance may not be provided.  Perform 
additional tightening of the tightening cap of AC 
cover and communication cover regularly. 

 

 

5. Tighten the tightening cap of communications 
cover to the specified torque. 
6. Use a wire with a cross-sectional area of 0.3 mm

2

 

and a cable with diameter of 4 mm is allowed for 
the communications plug. 
7. Tightly tighten the screws of plug with Data 
Logger. 

 

 

 

 

 

 

 

 

Содержание KP100G

Страница 1: ...KP100G Technical manual Grid Connect Photovoltaic Inverter Part number 1868180 8 A...

Страница 2: ...S YES 3 Conditions for Disconnecting from the Grid 12 YES YES 4 Parts Names 13 YES YES Installation 15 YES Mounting 15 YES Package Contents 15 YES Mounting Dimensions 16 YES Mounting Procedure 17 YES...

Страница 3: ...damage refers to damage that may extend to include the house furniture and pets Meanings of Alert Symbols Disassembly Prohibition Indicates prohibitions when there is a possibility of injury such as...

Страница 4: ...ctor the AC output cover RS 485 protection cover and the RS 232C protection cover Do not unfasten of cable gland of AC output and RS 485 Significant property damage may occasionally occur Do not use t...

Страница 5: ...tion that will be able to support its weight 35 kg The installation location must be able to withstand the force of 185 N m of torque at each mounting screw Injury or electric shock will occur Read th...

Страница 6: ...MC connector Electric shock will occur Doing AC wiring work during Turn OFF the AC breaker before connecting the MC connector Electric shock will occur Do not touch the DC plug or MC connector for at...

Страница 7: ...he AC connection 18 When wiring to the AC connection do not put two or more wires into one wire insertion opening 19 Omron KP100G PV Inverter shall be installed and used properly in a way to keep away...

Страница 8: ...maintained or overhauled except by OMRON or any person expressly authorized by OMRON without prior written consent of OMRON b use of parts or accessory other than OMRON specify c defect caused by circ...

Страница 9: ...0G 9 2 Model Name The following KP100G models are available Table 2 1 Model Name Model ENS Availability Country KP100G OD DE With ENS Germany KP100G OD ES Without ENS Spain KP100G OD IT Without ENS It...

Страница 10: ...rackers DC Bus The three sets of MPP Trackers store DC power via the DC DC boost converter to the DC bus DC AC Inverter The DC bus is connected to the DC AC inverter which converts DC power to AC powe...

Страница 11: ...re not in danger of being injured For this purpose a new safety concept was added to the VDEW regulations proposed by Berufsgenossenschaft fuer Feinmechanik und Elektrotechnik German Employee Associat...

Страница 12: ...voltage exceeds 100 UN in 10min the KP100G disconnect from grid Grid Frequency When the grid frequency varies from the ranges listed in Table 3 2 the KP100G disconnects from the grid Table 3 2 Condit...

Страница 13: ...imultaneously In the meantime air cooling fans will dissipate heat from inside of the inverter to outside or top to down direction Fig 4 2 Cooling fans 2 3 pairs of DC input terminals MC connectors Ea...

Страница 14: ...RS 485 The port is protected by a water proof cover Fig 4 5 RS 485 communication interface 5 RS 232 communication interface Interface allows communication with computer via RS 232C serial Fig 4 6 RS...

Страница 15: ...o process the communications plug and AC plug 22 5 Wiring the Unit Wire the KP100G to the grid and to the solar modules as described in Fig 5 34 and Fig 5 35 on the reference page 28 6 Preliminary Con...

Страница 16: ...For connection of RS 485 cable Fig 5 3 Rubber Bushing Securing plate and screws for removable data logger Securing plate screws Fig 5 4 Securing plate and screws MC caps MC caps Fig 5 5 MC caps Mount...

Страница 17: ...mum between the Unit and the ceiling or eave 20 cm minimum between the Unit and the floor or ground and 20 cm minimum between the Unit and right or left wall Fig 5 7 Mounting conditions 1 4 When insta...

Страница 18: ...ake voltage variation larger and cause a malfunction it may result in a claim to replace the product d Nearby plant under a poor grid connection make voltage and or frequency vary too largely to activ...

Страница 19: ...tall the device to a narrow upright mark the 4 central holes at the back of the bracket as illustrated in Fig 5 11 Fig 5 10 Mounting holes Fig 5 11 Mounting holes to install the device to a narrow upr...

Страница 20: ...screws and tighten Outer Mounting Holes Central Mounting Holes Fig 5 12 Mounting the base plate 3 Mount the PV Inverter onto the base plate as illustrated Fig 5 13 Mount the KP100G onto the base plat...

Страница 21: ...of it and pull out Fig 5 14 Detach the securing plate 2 Insert 2 screws and tighten to attach the securing plate to data logger Fig 5 15 Attach the securing plate 3 Drill 2 holes in the wall and then...

Страница 22: ...used due to usage conditions with the result that IP65 performance may not be provided Perform additional tightening of the tightening cap of AC cover and communication cover regularly 5 Tighten the t...

Страница 23: ...th 1 hole is used for connection with multiple cable Rubber sealing for GND cable is already inserted inside of connector Now insert the four wires of the AC cable and one wire of GND cable into the b...

Страница 24: ...operly push the AC output connection set back in to the Connection Panel Drive 5 screws back to fix the set Fig 5 22 Set the AC output cover 6 Now screw on the cable glands to lock the bushing and cab...

Страница 25: ...in Fig 5 25 a Remove screws and pull out the fixed plate and RS 485 card a b Fig 5 25 Remove the protection cover and fixed plate 2 Prepare 2 pairs of shielded twisted wires for connection between th...

Страница 26: ...4 Fix the card with 2 screws as shown in Fig 5 29 Fig 5 29 Lock on the screws 5 Fix the protection cover with 4 screws as shown in Fig 5 30 Fig 5 30 Fix the protection cover Fixed plate R R T T R R T...

Страница 27: ...Fig 5 32 Fig 5 31 RS 232C interface Fig 5 32 Socket available for RS 232C connection KP100G uses a DB9 socket for the RS 232C interface Remove the DB9 socket cover before use The pin assignment of th...

Страница 28: ...tion condition Visual confirmation Make sure none of the mounting screws are loose Make sure that the KP100G and the mounting base plate are securely fixed with the main body mounting screw 3 Wiring c...

Страница 29: ...nel can be connected to 3 DC input as illustrated in Fig 5 35 b To fully optimize the PV output set up use the following configuration guidelines a For PV output less than 13A use a single pair of PV...

Страница 30: ...er ON delay time for grid connected operation See Note 1 Step 3 Confirm that the Data Logger LCD displays the status Normal and that the KP100G performs the grid connected operation The PV Inverter is...

Страница 31: ...protection intervenes By pressing the button once again the display will show the variation of the lower voltage threshold and the voltage value of the mains supply as measured by the micro controlle...

Страница 32: ...supply frequency are equal the inverter will switch to the fault status by doing so the inverter will disconnect from the grid and the display panel will show for example a message similar to T OK 50...

Страница 33: ...is pressed To save the power inverter should continue the lighting for 3 Minutes after the last activity But whenever a failure error occurs the backlight in red continues switch on and off alternati...

Страница 34: ...up automatically once DC power from the PV Panel is sufficient There are 4 modes of operation 1 States Standby Waiting Normal In this mode the KP100G automatically detects the system status and select...

Страница 35: ...y pressing key in text display the display is switched to daily display as above The principles of design are Time axis x axis 12 hours maximum can be displayed The first data of a day is plotted on t...

Страница 36: ...ial number of the inverter Version the firmware version of the inverter Memory the used percentage of total capacity Date The date setting in the RTC Real Time Clock Day The day of the week Time The t...

Страница 37: ...ction Channel selection Staus Normal Date Time 1 Select channel by 2 Press OK to change 3 Select parameter by using 4 Press OK to confirm and back 1 The display is shown from first data of a day 2 Up...

Страница 38: ...erter K3SC RS 232C RS 485 Interface Converter RS 485 Communications To communicate with multiple KP100G Units you can connect them to a personal computer via RS 485 ports The maximum cable length is 5...

Страница 39: ...munications cable for the last KP100G Unit in the series 0 3 mm2 shielded twisted pair cable is recommended for RS 485 connection Fig 8 2 Wiring KP100G Units to a personal computer RS 485 100 to 125 1...

Страница 40: ...case is provided by USB port of computer Use can not download via communication such as RS 232C and RS 485 For more information please contact the store from which you purchased the product RS 232C C...

Страница 41: ...xxxx xxxx xxxxW Pcc xxxx xxxx xxxxW The individual DC input power Instantaneous Output power Pac xxxxxW Pac xxxxxW Pac xxxxxW Pca xxxxxW The real time output power in xxxx W Accumulated energy informa...

Страница 42: ...e permissible 800V GFCI active E2 3 Ground I Fault E2 3 Fehlerstrom E2 3 ERR DERIVACION E2 3 Err Dispersione Leakage current on ground conductor is too high Isolation failure E2 4 Isolation fault E2 4...

Страница 43: ...XXX XXX ENG ESP GER ITA Lingua XXX XXX ENG ESP DEU ITA Set up of the display language Warning Message Shown in warning row Memory is to be full MEMORY LEFT xx x memory left xx x MEMORIA LIBRE xx x Mem...

Страница 44: ...OD ES All pole disconnection grid side Mains monitoring with two independent allocated switching devices Over voltage Category III Self consumption during nighttime 3 5W or less External interfaces D...

Страница 45: ...Suspect a Problem Operation does not start immediately even though the connectors are correctly connected The power generation of the solar modules is insufficient Operation will begin when the sunlig...

Страница 46: ...vice is affecting the grid system 6 The setting of inverter is deviated from its default values 7 Inverter is abnormal 1 If this problem occurs seldom such as 1 time a day no action is necessary Opera...

Страница 47: ...stallation is less than 55 C 2 Check the space near the heat sink 3 Remove any obstacle that block the heat dissipation near heat sink 4 If the problem persists please replace the inverter A2 5 Fan Lo...

Страница 48: ...e on human life and property iv Equipment requiring a high level of reliability such as gas water or electrical supply systems and systems that operate 24 hours a day v Other applications requiring a...

Страница 49: ...KP100G 49 14 Appendix Certificates for the KP100G CE mark self declaration of conformity VDE0126 1 1 test report by TUV RD1663 2000 self declaration DK5940...

Страница 50: ...KP100G 50 EC DECLARATION OF CONFORMITY...

Страница 51: ...KP100G 51 Technical Report...

Страница 52: ...KP100G 52 Declaration of Conformity RD1663 2000...

Страница 53: ...KP100G 53 Declaration of Conformity DK5940...

Страница 54: ...ccidentally enters the product When you contact the store provide them with the following information Type Serial number Purchase date Details of the problem A description of the malfunction Your addr...

Отзывы: