3. System Description
The KP100G converts DC power obtained from solar modules into the AC power that is used in homes and businesses, and enables interconnection
with the utility grid.
This makes it possible to purchase power from the utility during periods when the load is high, and to sell power to the utility during periods when the
load is low. (Please note that a contract must be concluded with the utility for this purchasing and selling transaction.) The system configuration of the
KP100G is shown in Fig, 3-1.
Fig, 3-1 System configuration of KP100G
MPP (Maximum Power Point) Trackers
Three pairs of positive and negative DC input channels are connected to three sets of MPP Trackers.
DC Bus
The three sets of MPP Trackers store DC power via the DC/DC boost converter to the DC bus
DC/AC Inverter
The DC bus is connected to the DC/AC inverter, which converts DC power to AC power
Main and Redundant Relays
The two relays, RLY1 and RLY2, control the connection of the inverter to grid via the main and redundant controllers.
Output Lines
Three output lines (L1, L2, and L3) represent the three-phase AC power transmission to grid.
Other Main Components
The EMI Filter, GFCI, System Power Supply, Riso, Interface, and Display are included.
EMI Filte
r
EMI Filte
r
System
Power
Main Controller
Redundant
Controller
Interface
RS-485, RS-232C
Display
GFCI
MPP Tracker 1
+
+
MPP Tracker 2
MPP Tracker 3
PV1+
PV1
-
PV2+
PV2
-
PV3+
PV3
-
DC/AC Inverter
L1
L2
L3
N
PE
L V
VAC
VO
U
ACI
BUS_V
Riso
DCI
DC
V
RLY1
RLY2
Vdc1, Vdc2, Vd
c3
Idc1, Idc2,
Idc3
BU
S_V
Iac1, I
ac2, I
ac3
GFCI_V
Vac1, V
ac2, V
ac3
Vout1,Vout2,Vout3
Содержание KP100G
Страница 1: ...KP100G Technical manual Grid Connect Photovoltaic Inverter Part number 1868180 8 A...
Страница 50: ...KP100G 50 EC DECLARATION OF CONFORMITY...
Страница 51: ...KP100G 51 Technical Report...
Страница 52: ...KP100G 52 Declaration of Conformity RD1663 2000...
Страница 53: ...KP100G 53 Declaration of Conformity DK5940...