Hold Measured Value
The following is for when the K3TS is set to
.
When the HOLD input is turned ON, measurement stops and the input value
measured just before the HOLD input is turned ON is held. The displayed
value, comparative outputs, and BCD data are also held while the HOLD in-
put is ON. When the HOLD input is turned OFF, the held data is released.
If power is switched ON while the HOLD input is ON, the reset state is re-
garded as the input value. “
” is displayed in this case. Make sure the
HOLD input is OFF before applying power. The following graph illustrates the
effect of this operation.
Display value
(input value)
HOLD input
H set value
H comparative output
L comparative output
Forced Zero (Zero-shift)
With the ZERO input ON (by short-circuiting the ZERO input), the process
value can be shifted to zero. This condition is held until the next ZERO input
signal is turned ON.
Input value
Displayed value
OFF
ON
ZERO input
ZERO indicator
0
0
ON
The value is calibrated to zero at the rising edge of the ZERO input.
The ZERO indicator on the front panel is lit.
#
Section 6-3
Содержание K3TS
Страница 1: ...K3TS Intelligent Signal Processor Operation Manual Revised August 1997...
Страница 2: ......
Страница 4: ......
Страница 5: ...0 1 2 3 4 5 0 5 2 0 4 6 7 89 6 9 0...
Страница 6: ......
Страница 8: ...9 1 4...
Страница 11: ...1...
Страница 16: ...1...
Страница 20: ...1 1...
Страница 22: ...1...
Страница 24: ...1 1 1 91 0 8 91 8...
Страница 68: ...1 1 0 1...
Страница 73: ...1 6 2 3 4 5 0 5 2 0 4 6 7 89 6...
Страница 85: ...6 1 5...
Страница 96: ...2 2 324 4 4 72 70 4 0 2 0 2 0 324 5 6 324 4 3 324 5 6 324 4 3 72 0 2...