2-1
K3TS-SD
B-
(with Set Value LED Display)
The following diagram identifies the major features found on the K3TS with
Set Value LED Display front panel. The table gives a brief description of the
function of each front panel feature.
4. PV display status indicators
8. Operation keys
7. Unit
1. PV display
6. Bank indicators
2. SV display
5. SV display status
indicators
3. Comparative output status indicators
No.
Name
Functions
1
PV (process value)
display
Displays the process, maximum, and minimum values. Displays characters indicating
the set mode and set values. Displays an error message when an error occurs.
2
SV (set value) display
Displays the set value of a comparative output. In setting mode, displays the set
parameter.
3
Comparative
output status
indicators
HH
Is lit when HH comparative output status is ON. HH comparative output status turns
ON when the measured value exceeds the HH set value.
H
Is lit when H comparative output status is ON. H comparative output status turns ON
when the measured value exceeds the H set value.
L
Is lit when L comparative output status is ON. L comparative output status turns ON
when the measured value falls below the L set value.
LL
Is lit when LL comparative output status is ON. LL comparative output status turns ON
when the measured value falls below the LL set value.
PASS
Is lit when PASS comparative output status is ON. PASS comparative output status
turns ON when all HH, H, L, and LL comparative output status are OFF.
4
PV display
status
indicators
HOLD
Is lit when HOLD input is ON. By turning ON the HOLD terminal on the rear panel, the
hold function can be effected.
TIMING
Is lit when the TIMING input is ON. By turning ON the TIMING terminal on the rear
panel, the TIMING hold function can be effected.
Min
Indicates that the value displayed on the PV display is the minimum value. To display
the minimum value, use the DATA TEACH Key.
Max
Indicates that the value displayed on the PV display is the maximum value. To display
the maximum value, use the DATA TEACH Key.
ZERO
Is lit when ZERO shift status is ON. By turning ON the ZERO terminal on the rear
panel, the ZERO shift function can be effected.The ZERO indicator is lit when the
display value is shifted if the model has a display shift function.
5
SV display status
indicators
Indicates whether the displayed set value on the SV display is HH and LL or H and L.
The SV display is lit when the set values are HH and LL and not lit when the set values
are H and L.
Section 2-1
Содержание K3TS
Страница 1: ...K3TS Intelligent Signal Processor Operation Manual Revised August 1997...
Страница 2: ......
Страница 4: ......
Страница 5: ...0 1 2 3 4 5 0 5 2 0 4 6 7 89 6 9 0...
Страница 6: ......
Страница 8: ...9 1 4...
Страница 11: ...1...
Страница 16: ...1...
Страница 20: ...1 1...
Страница 22: ...1...
Страница 24: ...1 1 1 91 0 8 91 8...
Страница 68: ...1 1 0 1...
Страница 73: ...1 6 2 3 4 5 0 5 2 0 4 6 7 89 6...
Страница 85: ...6 1 5...
Страница 96: ...2 2 324 4 4 72 70 4 0 2 0 2 0 324 5 6 324 4 3 324 5 6 324 4 3 72 0 2...