What can be done by the setting tool
E
2. Zone Overlap Condition
A condition to configure setting zones as overlapped.
Except for combination of muting zone and fixed blanking zone (figure 3), setting zones of these 4
functions cannot be configured as overlapped. (Figure 4)
Zone overlap condition
: Setup available
x: Setting not possible
Even if a muting zone and a fixed blanking zone are configured as overlapped, fixed blanking monitoring function is
effective. Thus a fixed blanking beam receives light under muting, operation is based on setting of the monitoring
function.
Muting Function
Fixed Blanking
Function
Floating Blanking
Function
Warning Zone
Function
Muting Function
-
x
x
Fixed Blanking Function
x
x
x
Floating Blanking Function
x
x
-
x
Warning Zone Function
x
x
x
-
Muting zone
Fixed blanking zone
Floating blanking zone
Fixed blanking zone
Muting zone
Alarm zone
Figure 4
Figure 3