F3SJ-A
User’s Manual
What can be done by the setting tool
Setting Adjusted to Application
Fixed Blanking Function
Overview
Disables F3SJ’s specified beams.
Install protective structure for all zones of disabled zone so that a worker should not be
able to approach hazardous zone of a machine without passing through zones disabled
by the fixed blanking function.
Otherwise it may result in serious injury.
If allowable beams are designated for fixed blanking, detection capability gets larger near
an object that interrupts beams. Calculate a safety distance based on the setting.
Otherwise, the machine may not stop before a person reaches the hazardous part,
resulting in serious injury.
You must ensure that a test rod should be detected in all zones where it should be
detected after setting the fixed blanking function. Failure to do so may result in serious
injury.
Example
•A belt conveyor must be ignored which always sits in a detection zone.
Functional Description
• Fixed Blanking Function
A function that disables a part of F3SJ's detection zone. Safety output will be kept ON status even if an
object exists in the disabled zone.
For beams with fixed blanking designation, one zone is set for beams in concatenation, and up to 5
zones can be set as fixed blanking zones.
• Fixed Blanking Zone Setting
An zone for fixed blanking zone must be configured. It is possible to perform teaching and set the
designated beams manually with the interrupting object placed in the appropriate position. In this
example shown below, the 5th and 10th beams are set as bottom and top beams respectively.
- Upper Beams: Indicate beams on F3SJ’s terminal.
Lower Beams: Indicate beams on F3SJ’s power supply end.
- Only one zone can be configured as a fixed blanking zone by the setting console.
- Up to 5 zones can be configured as fixed blanking zones by the PC tool for F3SJ.
- To reconfigure F3SJ, for which multiple zones have been already configured by the PC tool for F3SJ, setting
recovery (to factory shipment setting) must be executed before the reconfiguration.
To configure multiple zones, use the PC tool for F3SJ.
Fixed blanking zone
10th beam
5th beam
Upper
Upper
Lower
Lower
Содержание F3SJ Series
Страница 1: ...F3SJ A N Series Version 2 Safety Light Curtain User s Manual Cat No SCHG 719K...
Страница 19: ...xvii F3SJ A User s Manual Introduction Contents E Revision History 202...
Страница 20: ...xviii Introduction Contents F3SJ A User s Manual...
Страница 44: ...24 Chapter 1 Compatibility with former version F3SJ A User s Manual Overview and Specifications...
Страница 184: ...164 Chapter 4 Wiring F3SJ A User s Manual Wiring Installation...
Страница 192: ...172 Chapter 5 Wiring Examples F3SJ A User s Manual Input Output Circuit and Applications...