System Configuration and Functions
•T3: Muting input time with allowable waveform cracks
This is the maximum value for the waveform cracks allowed for muting input 1 and 2 when muting is
in effect. It is set to 0.1 sec.
Installation Example 2 of Standard Muting Mode (using 4
muting sensors)
This installation example uses 4 through-beam type photoelectric sensors as muting sensors.
The use of 4 muting sensors is useful when the length of the workpieces (L) is constant or longer.
1.
Before a workpiece passes through
All muting sensors are turned OFF and the safety function of the F3SJ is working.
2.
The muting sensors are blocked and the safety function of the F3SJ is disabled
When muting sensors A1 and B1 are turned ON in this order, the muting function is enabled. In this
state, the safety function of F3SJ is disabled.
A1
B1
F3SJ
A2
B2
V
D3
L
d2
D2
Workpiece
Hazardous zone
d2: Maximum distance required for the muting sensor to keep the muting function enabled
D2, D3: Minimum distances required for the muting sensor to keep the muting function enabled
A1
F3SJ
B2
B1
A2
Workpiece
Hazardous zone
Содержание F3SJ Series
Страница 1: ...F3SJ A N Series Version 2 Safety Light Curtain User s Manual Cat No SCHG 719K...
Страница 19: ...xvii F3SJ A User s Manual Introduction Contents E Revision History 202...
Страница 20: ...xviii Introduction Contents F3SJ A User s Manual...
Страница 44: ...24 Chapter 1 Compatibility with former version F3SJ A User s Manual Overview and Specifications...
Страница 184: ...164 Chapter 4 Wiring F3SJ A User s Manual Wiring Installation...
Страница 192: ...172 Chapter 5 Wiring Examples F3SJ A User s Manual Input Output Circuit and Applications...