17
Startup Procedure
Section 2-2
2-2
Startup Procedure
2-2-1
Simple I/O Allocation
Use this method in the following situations.
• To allocate words in the master only for basic data, such as the set points
(SPs), process values (PVs), and alarm outputs for each Temperature
Controller.
• To use the DeviceNet Communications Unit without a Configurator (when
allocating only fixed I/O in the master).
Step
Item
Details
Reference
page
8
Set the I/O allocation method.
Set simple I/O allocation as the method for allocating I/O
data in the IN and OUT Areas used by the DeviceNet
Communications Unit. Turn ON pin 1 of the DIP switch.
Set DIP switch pin 2 to the model of the Temperature
Controller connected.
25
9
Set the highest unit number of the
connected Temperature Control-
lers.
Set the highest communications unit number of the Tem-
perature Controllers connected to the DeviceNet Com-
munications Unit using the rotary switch (Max. No.) of
the Unit. This setting will determine the size of the IN and
OUT Areas.
26
10
Connect the DeviceNet communi-
cations connectors.
Connect the DeviceNet communications connector to the
DeviceNet Communications Unit.
Note
Do not turn ON the communications power sup-
ply at this time.
This power supply is also used as the internal cir-
cuit power supply of the DeviceNet Communica-
tions Unit.
32
11
Turn ON the power to the End Unit. Turn ON the power connected to the End Unit.
Note
The Temperature Controllers will start.
---
12
Turn ON the DeviceNet communi-
cations power
(V+, V
−
).
Turn ON the communications power supply to the
DeviceNet Communications Unit. (See note.)
Note
The DeviceNet Communications Unit will start.
---
13
Check the indicators on the
DeviceNet Communications Unit.
Check that the status of each indicator on the DeviceNet
Communications Unit is as follows:
MS:
Operating normally when lit green.
NS: Operating normally when lit green. (DeviceNet
online or communications connected)
TS:
Communicating with Temperature Controllers
when lit green.
23
14
Operate from the Configurator (if
user-set allocation is used at the
master).
Note
This also applies if 11 or
more TC4 Units are con-
nected.
With the Configurator online, open the master's Edit
Device Parameters Window and allocate the IN and OUT
Areas used by DeviceNet in the master. Click the Master
I/O Allocations Tab, specify the first words for allocation
input 1 and allocation output 1, and download the param-
eters to the master.
Note
When fixed allocations are used, I/O is allocated
automatically.
73
Содержание EJ1 - 07-2008
Страница 1: ...DeviceNet Communications Unit for EJ1 Temperature Controllers Cat No H155 E1 02 OPERATION MANUAL...
Страница 2: ...DeviceNet Communications Unit for EJ1 Temperature Controllers Operation Manual Revised July 2008...
Страница 3: ...iv...
Страница 19: ...xx...
Страница 33: ...14 Initial Temperature Controller Settings Section 1 4...
Страница 53: ...34 Wiring the Temperature Controllers Section 3 4...
Страница 101: ...82 Ladder Programming Examples Section 4 6...
Страница 143: ...124 Sending Explicit Messages Section 6 5...
Страница 155: ...136 Message Communications Characteristics Section 7 2...
Страница 163: ...144 Maintenance Section 8 2...
Страница 189: ...170 Allocation Numbers for Configurators Manufactured by Other Companies Appendix B...
Страница 197: ...178 Index...