107
Overview of Explicit Message Communications
Section 6-1
Error Code
The following table shows the error codes for explicit messages.
6-1-4
Initializing the DeviceNet Communications Unit or Temperature
Controllers
Set the DeviceNet message monitor timer for the DeviceNet Communications
Unit to 5 s or longer using the following procedure.
CS/CJ-series DeviceNet Unit
1,2,3...
1.
Using the Configurator, select
Connection
from the Network Menu to
switch to online operation.
2.
Double-click the icon for the master, and then click the
Message Timer
Tab in the Edit Device Parameters Window.
3.
Double-click the icon for the DeviceNet Communications Unit, set the timer
to 5000 ms in the Setup Message Timer Dialog Box, and then click the
OK
Button. (In this example, the node address of the DeviceNet Communica-
tions Unit is 00.)
Error
code
Error name
Cause
08FF Service not supported
The service code is incorrect.
09FF Invalid Attribute Value
The specified attribute value is not supported. The
data written is out of the data range.
0CFF Object State Conflict
There is a error in the communications between the
DeviceNet Communications Unit and the Tempera-
ture Controller.
Another explicit message was received while a pre-
vious explicit message was being processed.
The copy function is being executed.
0EFF Attribute Cannot Be Set A write service code was sent for a read-only
attribute ID.
10FF Device State Conflict
An attempt was made to access a Temperature Con-
troller that does not exist.
There is an error in the EEPROM.
13FF Not Enough Data
The data string is shorter than the specified size.
14FF Attribute Not Supported The specified attribute is not supported.
15FF Too Much Data
The data string is longer than the specified size.
16FF Object Does Not Exist
The specified instance ID is not supported.
19FF Store Operation Failure There is an error in the EEPROM of the DeviceNet
Communications Unit.
Содержание EJ1 - 07-2008
Страница 1: ...DeviceNet Communications Unit for EJ1 Temperature Controllers Cat No H155 E1 02 OPERATION MANUAL...
Страница 2: ...DeviceNet Communications Unit for EJ1 Temperature Controllers Operation Manual Revised July 2008...
Страница 3: ...iv...
Страница 19: ...xx...
Страница 33: ...14 Initial Temperature Controller Settings Section 1 4...
Страница 53: ...34 Wiring the Temperature Controllers Section 3 4...
Страница 101: ...82 Ladder Programming Examples Section 4 6...
Страница 143: ...124 Sending Explicit Messages Section 6 5...
Страница 155: ...136 Message Communications Characteristics Section 7 2...
Страница 163: ...144 Maintenance Section 8 2...
Страница 189: ...170 Allocation Numbers for Configurators Manufactured by Other Companies Appendix B...