Chapter 3
3-20
Operation
3-6-5 Selecting the Processing after Recovery from a
Momentary Interruption
• Use this parameter to select the processing to be performed when a momentary power interruption
occurs.
• When setting 1 or 2 is selected, an alarm is output when low voltage is detected in the main circuit,
and the alarm is automatically cancelled when the normal voltage resumes.
• If the power interruption is longer that the time for which Inverter operation can be performed, the
operation after recovery from the power interruption will be the same as the startup operation.
3-6-6 Selecting Operation Commands
• This parameter selects the input method for specifying Inverter starting, stopping, and direction of
rotation.
• There are two methods that can be selected for operation commands. Select the best method for
the application.
P08
Frequency reference lower limit
Changes during
operation
No
Setting range
0.1 to 120 (Hz)
Setting unit
0.1 Hz (See note.)
Default setting
0.0
P09
Momentary power interruption restart selection
Changes during
operation
No
Setting range
0 to 2
Default setting
0
Set value
Description
0 (
0
)
Inverter stops operating. (If the interruption lasts for 15 ms or longer, main circuit low voltage
will be detected and an error will occur.)
1 (
1
)
Inverter continues operating if power interruption is 0.5 s or less. (If a power interruption
occurs when
1
is set for 0.5 s, the main circuit low voltage is detected and outputs are
stopped while waiting for power to be restored. If power is restored within 0.5 s, operation
resumes.)
2 (
2
)
Inverter always continues operating. (If a power interruption occurs when
2
is set, outputs are
stopped while waiting for power to be restored. When power is restored, outputs are
resumed.)
P10
Operation command selection
Changes during
operation
No
Selected item
Key/PLC
Default setting
Key
Selected item
Description
Key (
key
)
Operation commands are performed using the Digital Operator keys.
PLC (
plc
)
Operation commands are performed using the STF and STR control inputs.
Содержание EasySpeed 3G3JE
Страница 1: ...3G3JE Compact Simplified Inverters Cat No I547 E1 02 USER S MANUAL...
Страница 3: ...USER S MANUAL 3G3JE Compact Simplified Inverters...
Страница 18: ...Table of Contents XVI...
Страница 19: ...Chapter 1 Overview 1 1 Functions 1 2 Nomenclature...
Страница 23: ...Chapter 2 Design 2 1 Installation 2 2 Wiring...
Страница 86: ...Chapter 3 3 26 Operation...
Страница 100: ...Chapter 4 4 14 Maintenance Operations...
Страница 101: ...Chapter 5 Specifications 5 1 Inverter Specifications 5 2 Option Specifications...
Страница 112: ...Chapter 5 5 12 Specifications...
Страница 113: ...Chapter 6 Parameter Tables...
Страница 118: ...Chapter 6 6 6 Parameter Tables...
Страница 119: ...Chapter 7 Appendix 7 1 Selecting the Inverter 7 2 Precautions on Using the Inverter for a Motor...
Страница 130: ...Chapter 7 7 12 Appendix...
Страница 132: ...R 2 Revision History...