Chapter 5
5-3
Specifications
Note 1.
The required capacity at the facility is the capacity for the Inverter's rated output. It depends
on the impedance at the input power supply. (The input power supply's power factor fluctu-
ates, so it can be improved by inserting an AC reactor.) There will also be variations in the
ratio between the rated current of the motor that is used and the rated output current of the
Inverter.
Note 2.
The heat radiation is the electric power consumed in the Inverter at the Inverter's rated out-
put. (It is calculated by subtracting the output power from the input power under rated oper-
ating conditions.)
Protective
functions
Motor protection
Protection by electronic thermal
Instantaneous overcurrent protec-
tion
Stops at approx. 250% of rated output current.
Overcurrent protection
Stops in 1 min at approximately 150% of rated output cur-
rent.
Overvoltage protection
Stops when main-circuit DC voltage is approximately 410 V
min.
Undervoltage protection
Stops when main-circuit DC voltage is approximately 200 V
max.
Momentary power interruption
restart selection
Select between none (stops at 15 ms or longer), continue
operation if power is restored within approx. 0.5 s, or con-
tinue operation regardless of length of interruption.
Radiation fin overheated
Temperature is detected by a thermistor.
Grounding protection
Protected by overcurrent protection.
Charge indicator
The data display will flash until the main circuit DC voltage
is 60 V or less.
Environ-
ment
Location
Inside a control panel (with no corrosive gas, dust, etc.)
Ambient operating temperature
−
10
°
C to 50
°
C
Ambient operating humidity
5% to 85% (with no condensation)
Transport and storage temperature
−
20
°
C to 60
°
C
Transport and storage humidity
5% to 85% (with no condensation)
Altitude
1,000 m max. (air pressure of 79.5 kPa min. during trans-
port and storage)
Insulation resistance
5 M
Ω
min.
Vibration resistance
9.8 m/s
2
max.
Degree of protection
IP20
Item
Three-phase 200-V AC models
(3G3JE)
A2001
A2002
A2004
Содержание EasySpeed 3G3JE
Страница 1: ...3G3JE Compact Simplified Inverters Cat No I547 E1 02 USER S MANUAL...
Страница 3: ...USER S MANUAL 3G3JE Compact Simplified Inverters...
Страница 18: ...Table of Contents XVI...
Страница 19: ...Chapter 1 Overview 1 1 Functions 1 2 Nomenclature...
Страница 23: ...Chapter 2 Design 2 1 Installation 2 2 Wiring...
Страница 86: ...Chapter 3 3 26 Operation...
Страница 100: ...Chapter 4 4 14 Maintenance Operations...
Страница 101: ...Chapter 5 Specifications 5 1 Inverter Specifications 5 2 Option Specifications...
Страница 112: ...Chapter 5 5 12 Specifications...
Страница 113: ...Chapter 6 Parameter Tables...
Страница 118: ...Chapter 6 6 6 Parameter Tables...
Страница 119: ...Chapter 7 Appendix 7 1 Selecting the Inverter 7 2 Precautions on Using the Inverter for a Motor...
Страница 130: ...Chapter 7 7 12 Appendix...
Страница 132: ...R 2 Revision History...