Typical Example 2

Input type: 

4 T thermocouple 

200 to 400

°

C

Control method:  PID control

Calculate PID constants using AT (auto-tuning).

Alarm type:

2 upper limit

Alarm value 1:

30

°

C

Set point:

150

°

C

E5ZN unit number: 1

Channel number:

2

Check the alarm type.

Operation Level

Start operation

Set the channel number.

Set the unit number.

Set the control method.

Set the alarm type.

Set input specifications.

Power ON

Process 
value/set point

Input type

For ON/OFF 
control

Control period (OUT1) 
(unit: seconds)

For PID 
control

Control stops.

Operation Level

Initial Setting Level

Press the      Key for at least 3 s.

Set the unit number using the 

UNIT

 Key.

AT ends and operation starts.

Initial Setting Level

Set the channel number using the 

CH

 Key.

Alarm 1 type

Press the    . Key for at least one second.

Set to 

pid

 when PID control is used.

M

M

M

M

Power ON

Process value/
set point

To
operate

Alarm value 1

To stop

Operation level

M

M

M

PV/SP
After AT execution.

During AT execution.

SP will flash while AT 
is being executed.
After AT execution.

During AT execution.

Press the      Key (for less than 1 s).

To execute AT

Execute AT.

Adjustment Level

Press the     Key for less than one second.

To stop AT

AT execution

Adjustment Level

(for PID control)

Use the 

U

 and 

D

 Keys to set the 

input type to 4.

Use the 

U

 and 

D

 Keys to check 

that the control is 
PID.

Check the control 
period.

Check the alarm 
type.

Press the 

U

 and 

D

 Keys to set the 

set point to 150

°

C.

Press the 

U

 and 

D

 Keys to set the 

alarm value to 
30

°

C.

Select "Run" 
using the 

U

 and 

D

 Keys.

Set to 

on

 to execute AT and 

to 

off

 to stop AT.

Recommended settings: 20 s for a 
relay output and 2 s for a voltage/
SSR output.

Setup Procedure

Содержание E5ZN Series

Страница 1: ...is turned ON ERROR Lights when an input error e g memory error or input error for any channel occurs SD RD Send Data Receive Data Light during communications with the host OUT1 OUT2 Control Output 1 C...

Страница 2: ...rollers are mounted side by side Mounting Terminal Units Together From 0 to 15 Expansion Terminal Units E5ZN SCT18S can be connected to a standard Terminal Unit E5ZN SCT24S Terminal Units can be mount...

Страница 3: ...control panel DIN Track PFP 50N 50 cm PFP 100N 100 cm Install the DIN Track vertically to the ground Mounting the Controller Mounting Procedure Firmly insert the Controller following the guides on th...

Страница 4: ...r limit Alarm value 1 20 C Set the deviation in Set point 100 C E5ZN unit number 3 Channel number 1 Power ON Start operation Set the channel number Set the unit number Set the control method Set the a...

Страница 5: ...Key Alarm 1 type Press the Key for at least one second Set to pid when PID control is used M M M M Power ON Process value set point To operate Alarm value 1 To stop Operation level M M M PV SP After...

Страница 6: ...1 s to start the download Note 1 down will flash on Display No 2 during the download 2 The mode will return automatically to the Operation Level when the download has been completed Supplementary Exp...

Страница 7: ...in the download unit number display At initialization there is no upload data so the unit number display is blank Step 7 Press the UNIT Key for at least 1 s to start the download down will flash on th...

Страница 8: ...our levels are selected It is possible to enter Copy Mode while control is being performed but copy operations e g upload and download can be used only when control has stopped Mode Level During opera...

Страница 9: ...the Operation Level or Adjustment Level The first display flashes after 1 s The Initial Setting Level is for specifying the input type selecting the control method setting the control period setting...

Страница 10: ...l h 105 0 1 0 ol l 5 0 1 0 sero off u 0 hbh 0 1 1 0 M ot 2 0 u 0 M amoV 0 u 0 sedu 3 u 0 M istp 0 u 0 cjc on u 0 sprt 0 1 0 M M M M M M M M M M M M M M M M M al3n n o 1 0 alh3 0 2 C 1 0 M M M sub4 17...

Страница 11: ...tection Upper limit temperature input shift value Lower limit temperature input shift value Proportional band Integral time Derivative time M wtpt off u 0 M M at off 1 0 ct 0 0 1 0 hb 0 0 1 0 sp 0 0 C...

Страница 12: ...0 0 F N 8 200 to1300 C 300 to 2300 F R 9 0 to 1700 C 0 to 3000 F S 10 0 to 1700 C 0 to 3000 F B 11 100 to1800 C 300 to 3200 F ES1A Infrared Tempera ture Sensor K10 to 70 C 12 0 to 90 C 0 to 190 F K60...

Страница 13: ...See notes 1 and 6 See note 5 See note 4 6 Upper limit alarm with standby se quence See note 6 7 Lower limit alarm with standby se quence 8 Absolute val ue upper limit 9 Absolute val ue lower limit 10...

Страница 14: ...99 999 9 Less than 1999 199 9 More than 9999 999 9 Control continues and operation is normal This message is displayed when the PV or PV SP is displayed Memory Error There is an error in the internal...

Отзывы: