Setup Guidance

The sensor input type, alarm type, control cycle, and other initial hardware settings that were made using DIP switches on previous models are 
now made using the setup display on the E5ZN-SDL. Change the setup display by pressing the 

LEVEL

 and 

MODE

 Keys. The amount of time the 

keys are pressed determines what parameter is entered.

Interpreting Typical Examples

Typical Example 1

M

M

M

This symbol means that 
there are further 
parameters. Keep pressing 
the 

MODE

 Key until the 

system switches to the 
intended parameter.

Changing Parameters

Changing Values

Set values in each 
display can be 
changed by pressing 
the 

U

 and 

D

 Keys. 

Input type:

0 K thermocouple 

200 to 1300

°

C

Control method: ON/OFF control

Alarm type:

2 upper limit

Alarm value 1: 20°C (Set the deviation in 

Set point:

100

°

C

E5ZN unit number: 3

Channel number:

1

Power ON

Start operation.

Set the channel number.

Set the unit number.

Set the control method.

Set the alarm type.

Set input specifications.

Set alarm values.

Power ON

Process value/
set point

Input type

For 
ON/OFF 
control

Alarm 1 type

For PID
control

Control stops.

Operation Level

Initial Setting Level

Press the      Key for at least three seconds.

Set the unit number and channel by 
pressing the UNIT and CH Keys.

Press the      Key for at least one second.

M

Process 
value/set point

To operate

Alarm value 1

To stop

Operation Level

M

Operation Level

Initial Setting Level

Operation Level

M

M

M

M

Select "Run" 
using the 

U

 and 

D

 Keys.

Press the 

U

 

and 

D

 Keys to 

set the alarm 
value to 20

°

C.

Press the 

U

 and 

D

 Keys to set the 

set point to 100

°

C.

Check the input 
type. 

Select ON/OFF 
control by using 
the 

U

 and 

D

 

Keys.

Check the alarm 
type.

Setup Procedure

Содержание E5ZN Series

Страница 1: ...is turned ON ERROR Lights when an input error e g memory error or input error for any channel occurs SD RD Send Data Receive Data Light during communications with the host OUT1 OUT2 Control Output 1 C...

Страница 2: ...rollers are mounted side by side Mounting Terminal Units Together From 0 to 15 Expansion Terminal Units E5ZN SCT18S can be connected to a standard Terminal Unit E5ZN SCT24S Terminal Units can be mount...

Страница 3: ...control panel DIN Track PFP 50N 50 cm PFP 100N 100 cm Install the DIN Track vertically to the ground Mounting the Controller Mounting Procedure Firmly insert the Controller following the guides on th...

Страница 4: ...r limit Alarm value 1 20 C Set the deviation in Set point 100 C E5ZN unit number 3 Channel number 1 Power ON Start operation Set the channel number Set the unit number Set the control method Set the a...

Страница 5: ...Key Alarm 1 type Press the Key for at least one second Set to pid when PID control is used M M M M Power ON Process value set point To operate Alarm value 1 To stop Operation level M M M PV SP After...

Страница 6: ...1 s to start the download Note 1 down will flash on Display No 2 during the download 2 The mode will return automatically to the Operation Level when the download has been completed Supplementary Exp...

Страница 7: ...in the download unit number display At initialization there is no upload data so the unit number display is blank Step 7 Press the UNIT Key for at least 1 s to start the download down will flash on th...

Страница 8: ...our levels are selected It is possible to enter Copy Mode while control is being performed but copy operations e g upload and download can be used only when control has stopped Mode Level During opera...

Страница 9: ...the Operation Level or Adjustment Level The first display flashes after 1 s The Initial Setting Level is for specifying the input type selecting the control method setting the control period setting...

Страница 10: ...l h 105 0 1 0 ol l 5 0 1 0 sero off u 0 hbh 0 1 1 0 M ot 2 0 u 0 M amoV 0 u 0 sedu 3 u 0 M istp 0 u 0 cjc on u 0 sprt 0 1 0 M M M M M M M M M M M M M M M M M al3n n o 1 0 alh3 0 2 C 1 0 M M M sub4 17...

Страница 11: ...tection Upper limit temperature input shift value Lower limit temperature input shift value Proportional band Integral time Derivative time M wtpt off u 0 M M at off 1 0 ct 0 0 1 0 hb 0 0 1 0 sp 0 0 C...

Страница 12: ...0 0 F N 8 200 to1300 C 300 to 2300 F R 9 0 to 1700 C 0 to 3000 F S 10 0 to 1700 C 0 to 3000 F B 11 100 to1800 C 300 to 3200 F ES1A Infrared Tempera ture Sensor K10 to 70 C 12 0 to 90 C 0 to 190 F K60...

Страница 13: ...See notes 1 and 6 See note 5 See note 4 6 Upper limit alarm with standby se quence See note 6 7 Lower limit alarm with standby se quence 8 Absolute val ue upper limit 9 Absolute val ue lower limit 10...

Страница 14: ...99 999 9 Less than 1999 199 9 More than 9999 999 9 Control continues and operation is normal This message is displayed when the PV or PV SP is displayed Memory Error There is an error in the internal...

Отзывы: