
Troubleshooting Procedures
Section 10-4
152
Note
1.
The time information in the CPU Unit is used in the CPU Bus Units.
2.
If the time information cannot be read from the CPU Unit, the time stamp
in the error log will be all zeros. This can occur due to CPU Unit startup
error, unit number errors, CPU error, and model number errors. If the time
is read out from a Programming Device, the time will be shown as all zeros
in the year 2000.
3.
The battery must be installed in the CS-series CPU Unit, the power turned
ON, and then the time set before the clock in the CPU Unit can be used.
The time will not be set correctly in the error log unless the clock time is set
correctly.
4.
An error record is not created in EEPROM when a CPU Bus Unit memory
error occurs.
10-4 Troubleshooting Procedures
The following procedures can be used to troubleshoot various problems in
system operation.
10-4-1 Startup Problems
0300
Parameter error; packet discarded Commands
Bit 15:
OFF
Bits 08 to 14: SNA
Bits 00 to 07: SA1
Responses
Bit 15:
ON
Bits 08 to 14: DNA
Bits 00 to 07: DA1
Check the command format and
set the correct command data.
---
0601
CPU Bus Unit error
Arbitrary
Restart the CPU Unit. If the prob-
lem persists, replace the FL-net
(Ver. 2.00) Unit.
Saved
0602
CPU Bus Unit memory error
01: Read
error
02: Write
error
06: Error log
Restart the CPU Unit. If the prob-
lem persists, replace the FL-net
(Ver. 2.00) Unit.
Saved
(except
for error
log)
Error
code
Meaning
Detailed error code
Correction
EE-
PROM
1st byte
2nd byte
RUN
HER
PER
P/S
Probable cause
Correction
Not lit Not lit Not lit Not lit Power is not being supplied to the CPU Unit
or the power supply voltage is too low.
Supply power.
Make sure that the correct voltage is being
supplied.
The mounting screws on the FL-net Unit
are loose.
Tighten the screws on the FL-net Unit.
An error occurred in the FL-net Unit.
Restart the PLC. If the problem persists,
replace the FL-net Unit.
Not lit ---
Lit
---
The same unit number is being used on
another Unit as well.
Correct the unit number setting and restart
the PLC.
The FL-net Unit is not registered in an I/O
table.
Use a CX-Programmer or Programming
Console to create a new I/O table.
Not lit Lit
---
---
The node address is set outside the range. Set the node number to between 01 and F9
Hex and restart the PLC.
An error occurred in the FL-net Unit.
Restart the PLC. If the problem persists,
replace the FL-net Unit.
Содержание CJ1W-FLN22
Страница 2: ......
Страница 3: ...CS1W FLN22 100Base TX CJ1W FLN22 100Base TX FL net Units Operation Manual Revised October 2010...
Страница 4: ...iv...
Страница 6: ...vi...
Страница 10: ......
Страница 14: ...xiv...
Страница 18: ...xviii...
Страница 26: ...xxvi Unit Versions of CS CJ series FL net Units 7...
Страница 40: ...Precautions Section 1 6 14...
Страница 50: ......
Страница 88: ...Allocated Words in the DM Area Section 4 4 62...
Страница 158: ...Command Response Reference Section 7 5 132...
Страница 170: ......
Страница 192: ...Inspections Section 10 6 166...
Страница 218: ...192 System Configuration Appendix A...
Страница 224: ...198 System Configuration Example Appendix B...
Страница 270: ...244 FL net Unit Support Software Ver 1 6 Appendix F...
Страница 276: ...250 International System of Units Appendix G...