Error Status
Section 10-2
148
10-2 Error Status
The FL-net Unit will output error status to the following word in the PLC Data
Area Interface of the CPU Unit. This information can be used in troubleshoot-
ing errors.
10-2-1 Unit Status (Unit to CPU Unit)
1,500 + (25
×
unit number) + 6
The corresponding bit will turn ON when an error occurs
IP address setting error
Transceiver error
EEPROM error
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
FA Link (Common Memory) Area allocation error
Data Link (PLC) Area allocation error
Token monitoring timeout error
FA link operation
Readable receive
Bit
Name
Correction
8
FA Link (Common Memory)
Area allocation error
This bit turns ON if there is a Common Memory allocation error in the local node
setting range of the FA Link (Data Link) settings. Use the CX-FLnet or FL-net Unit
Support Software to re-set the FA Link (Common Memory) allocation settings
9
Data Link (PLC) Area allo-
cation error
This bit turns ON if there is a PLC Area allocation error in the local node setting
range or another node setting range of the FA Link (Data Link) settings. Use the
CX-FLnet or FL-net Unit Support Software to re-set the FA Link (Common Memory)
allocation settings.
10
Token monitoring timeout
error
This bit turns ON if a token monitoring timeout occurs while the local node is hold-
ing the token. Processing may be delayed because of system traffic, so recheck the
system configuration or extend the token monitoring timeout setting with the CX-
FLnet or FL-net Unit Support Software.
12
IP address setting error
The following cannot be used as IP address settings.
• Host IDs that are all 0 or all 1.
• Network IDs that are all 0 or all 1.
• Subnetwork IDs that are all 1.
• Addresses beginning with 127 (7F Hex).
Reset the IP address.
14
Transceiver error
The communications cable may be disconnected. Make sure the cable is mounted
securely.
15
EEPROM error
Restart the PLC. If the problem persists, replace the FL-net Unit.
Содержание CJ1W-FLN22
Страница 2: ......
Страница 3: ...CS1W FLN22 100Base TX CJ1W FLN22 100Base TX FL net Units Operation Manual Revised October 2010...
Страница 4: ...iv...
Страница 6: ...vi...
Страница 10: ......
Страница 14: ...xiv...
Страница 18: ...xviii...
Страница 26: ...xxvi Unit Versions of CS CJ series FL net Units 7...
Страница 40: ...Precautions Section 1 6 14...
Страница 50: ......
Страница 88: ...Allocated Words in the DM Area Section 4 4 62...
Страница 158: ...Command Response Reference Section 7 5 132...
Страница 170: ......
Страница 192: ...Inspections Section 10 6 166...
Страница 218: ...192 System Configuration Appendix A...
Страница 224: ...198 System Configuration Example Appendix B...
Страница 270: ...244 FL net Unit Support Software Ver 1 6 Appendix F...
Страница 276: ...250 International System of Units Appendix G...