119
Command/Response Reference
Section 7-5
Command
[CMND
S
D
C]
S
D01000
+0
:2902 Hex
D
D02000
:First word of the stored responses
C
D00000
+0
:0002 Hex
No. of command data bytes
+1
:004E Hex
No. of response data bytes
(including command
and response codes)
+2
:0000 Hex
Remote (destination)
network address 0
(local network)
+3
:0010 Hex
Remote (destination)
node number 0
(local node number)
Remote (destination)
unit address 10 Hex
* Be sure to set the
unit address of the FL-net
(Ver. 2.00) Unit to the
Unit 10 Hex.
+4
:0000 Hex
Response required,
communication port no. 0,
number of retries 0
+5
:0000 Hex
Response monitoring time
(default: 2 s)
Response
D02000
+0
:2902 Hex
Response code
(completed normally)
+1
:0000 Hex
:
(Undecided)
+4
:0001 Hex
(Fixed)
+5
:004A Hex
=64+10=74 bytes
+6
:0001 Hex
+7
:0002 Hex
Destination node number 2
:
(Undecided)
+22
:0064 Hex
Transaction code 100
:
(Undecided)
+34
:Data (10-bytes long)
:
+38
Содержание CJ1W-FLN22
Страница 2: ......
Страница 3: ...CS1W FLN22 100Base TX CJ1W FLN22 100Base TX FL net Units Operation Manual Revised October 2010...
Страница 4: ...iv...
Страница 6: ...vi...
Страница 10: ......
Страница 14: ...xiv...
Страница 18: ...xviii...
Страница 26: ...xxvi Unit Versions of CS CJ series FL net Units 7...
Страница 40: ...Precautions Section 1 6 14...
Страница 50: ......
Страница 88: ...Allocated Words in the DM Area Section 4 4 62...
Страница 158: ...Command Response Reference Section 7 5 132...
Страница 170: ......
Страница 192: ...Inspections Section 10 6 166...
Страница 218: ...192 System Configuration Appendix A...
Страница 224: ...198 System Configuration Example Appendix B...
Страница 270: ...244 FL net Unit Support Software Ver 1 6 Appendix F...
Страница 276: ...250 International System of Units Appendix G...