149
Error Log
Section 10-3
10-2-2 Network Status (Unit to CPU Unit)
1,500 + (25
×
unit number) + 7
10-3 Error Log
This section describes the error log that is used to record errors that have
occurred during FL-net Unit operation.
10-3-1 Error Log
The error log records errors that have occurred during FL-net Unit operation.
Errors recorded in the log can be read by FINS command. (Refer to
Logged Errors
The following errors are recorded in the error log.
• Errors in network operation
• Errors in data transfers
• Error in the PLC
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
−
−
−
−
−
− −
−
−
Duplicate node number detected
Upper level operating signal error (PLC
operation stopped)
Frame standby
FL-net version mismatch detected
Duplicate Common Memory
Common Memory data in effect notification
Common Memory setting complete
Bit
Name
Correction
8
Duplicate node number
detected
This bit turns ON if two nodes have the same node number. All communications
stop and the HER LED indicator flashes.
9
Frame standby
This bit turns ON if a receive frame cannot be detected. The power may not be ON
at the other node or there is a problem on the communications path. Check the
other node and the communications path.
10
FL-net version mismatch
detected
This bit turns ON if you try to log on to an FL-net (Ver. 1.00) network. All communi-
cations stop and the HER LED indicator flashes. Make sure the network is config-
ured entirely of FL-net (Ver. 2.00) nodes. Once this flag turns ON, it will remain ON
until the power is turned OFF and back ON again or until the Unit is restarted.
12
Upper level operating sig-
nal error (PLC operation
stopped)
A stop error or a persistent error has occurred in the CPU Unit. Use the CX-Pro-
grammer to clear the error on the CPU Unit.
The routing table settings are incorrect. Correct the routing tables using CX-Inte-
grator.
13
Common Memory data in
effect notification
This bit turns ON if the Common Memory of the FL-net Unit receives data from all
the nodes and it starts to replace data in the CPU Unit.
14
Common Memory setting
complete
This bit turns ON if the FL-net Unit can log on to the Data Link with no Common
Memory allocation setting error in the Unit at the time it logs on to the network.
If this flag is OFF when the local node logs on, the local node cannot access the
Data Link and only has access to the message service and token.
15
Duplicate Common Mem-
ory
This bit turns ON if the same Common Memory is set for the local node that is
attempting to log on to the network and another node that is already logged on to
the network. In this case, the local node cannot access the Data Link and only has
access to the message service and token.
Содержание CJ1W-FLN22
Страница 2: ......
Страница 3: ...CS1W FLN22 100Base TX CJ1W FLN22 100Base TX FL net Units Operation Manual Revised October 2010...
Страница 4: ...iv...
Страница 6: ...vi...
Страница 10: ......
Страница 14: ...xiv...
Страница 18: ...xviii...
Страница 26: ...xxvi Unit Versions of CS CJ series FL net Units 7...
Страница 40: ...Precautions Section 1 6 14...
Страница 50: ......
Страница 88: ...Allocated Words in the DM Area Section 4 4 62...
Страница 158: ...Command Response Reference Section 7 5 132...
Страница 170: ......
Страница 192: ...Inspections Section 10 6 166...
Страница 218: ...192 System Configuration Appendix A...
Страница 224: ...198 System Configuration Example Appendix B...
Страница 270: ...244 FL net Unit Support Software Ver 1 6 Appendix F...
Страница 276: ...250 International System of Units Appendix G...