Command/Response Reference
Section 7-5
124
• Creates control data starting at D01000.
• Sends the WORD BLOCK READ (unspecified
node number) command to the FL-net Unit using
the CMND(490) instruction.
• Using data that is read: Stores the 100-word long
data from D02002 (read data) starting at word
0000.
• Turns OFF execute condition 000000.
DIFU(13)
000000
@XFER(70)
# 0064
D02002
0000
@MOV(21)
# 2903
D01000
@MOV(21)
# 0020
D01001
@MOV(21)
# 0000
D01002
@MOV(21)
# 0064
D01003
@CMND(490)
D01000
D02000
D00000
0000
00
A202
00
0000
00
A202
00
Execute
condition
Execute
condition