18
Part Names and Functions
Section 2-3
2-3-2
Indicators
Indicators show the operating status of the Unit. The relationship between the
indicator status and the Unit status is shown in the following table.
2-3-3
Unit Number Switches
Data exchange between the CPU Unit and ID Sensor Unit is performed using
words allocated to the Unit in the Special I/O Unit Area and in the DM Area.
The words allocated to the ID Sensor Unit in these two areas are determined
by the setting of the unit number switches on the Unit’s front panel.
2-3-4
Communications Test Switch
The communications test switch on the Unit’s front panel is used to switch
between Normal Mode and Test Mode.
Indicator
Name
Color
Meaning
RUN
RUN
Green
Lit
The ID Sensor Unit is operating normally.
Not lit
The ID Sensor Unit is stopped.
ERC
(Error I/O Controller)
Unit error
Red
Lit
An error has occurred in the ID Sensor Unit.
Not lit
No error has occurred in the ID Sensor Unit.
ERH
(Error at Host)
CPU Unit error
Red
Lit
An error has occurred in the CPU Unit.
Not lit
No error has occurred in the CPU Unit.
ERP
(Head Power Error)
Head power error
Red
Lit
An error has occurred in the power supply to the
R/W Head.
Not lit
The power supply to the R/W Head is normal.
Head 1 T/R
Communicating
Yellow
Lit
Communications are active.
NORM/ERR
Normal end
Green
Lit
Communications with the Data Carrier ended
normally.
Error end
Red
Lit
Communications with the Data Carrier ended in
an error.
Head 2 T/R
Communicating
Yellow
Lit
Communications are active.
NORM/ERR
Normal end
Green
Lit
Communications with the Data Carrier ended
normally.
Error end
Red
Lit
Communications with the Data Carrier ended in
an error.
CS1W-V600C11
CS1W-V600C12
Switch
No.
Unit
No.
Words
allocated in
Special I/O
Unit Area
Words
allocated in
DM Area
Words
allocated in
Special I/O
Unit Area
Words
allocated in
DM Area
0
Unit 0
CIO 2000 to
CIO 2009
D20000 to
D20099
CIO 2000 to
CIO 2019
D20000 to
D20199
1
Unit 1
CIO 2010 to
CIO 2019
D20100 to
D20199
CIO 2010 to
CIO 2029
D20100 to
D20299
:
:
:
:
:
:
94
Unit 94 CIO 2940 to
CIO 2949
D29400 to
D29499
CIO 2940 to
CIO 2959
D29400 to
D29599
95
Unit 95 CIO 2950 to
CIO 2959
D29500 to
D29599
(Cannot be set)
0
1
2
3 4 5 6
7
8
9
0
1
2
3 4 5 6
7
8
9
Status
Description
OFF
Normal status (factory setting)
ON
Communications test
TEST
ON
Содержание CJ - 12-2004
Страница 2: ...SYSMAC CS CJ Series ID Sensor Units Operation Manual Revised December 2004...