When using an Expansion I/O Rack, the Rack must also be grounded to the GR
terminal. The same ground can be used for all connections.
Ground to 100
Ω
or less.
OK
Ground to 100
Ω
or less.
OK
Wrong
Other
devices
Other
devices
Other
devices
If grounding results in operating errors, insulate the CPU Backplane and all
Expansion I/O Backplanes from the control panel. Refer to Using the Antinoise
Insulating Attachment on page 77 for details.
Crimp Terminals
The terminals on the Power Supply Unit are M3.5, self-raising terminals with
screws.
Use crimp terminals for wiring. Do not connect bare stranded wires
directly to terminals. Tighten the terminal block screws to the torque of 0.8 N
S
m.
Use crimp terminals (M3.5) having the dimensions shown below.
7 mm max.
7 mm max.
3-2-2 Standard I/O Unit Wiring
Caution
Check the I/O specifications for the I/O Units, and consider the following points.
•
Do not apply a voltage that exceeds the input voltage for Input Units or the
maximum switching capacity for Output Units. Doing so may result in break-
down, damage or fire.
•
When the power supply has positive and negative terminals, be sure to wire
them correctly.
Note To satisfy the EC Directives (Low-voltage Directives), provide reinforced insula-
tion or double insulation for the DC power source connected to the DC I/O Unit.
Use a separate power source for the DC I/O Unit from the external power supply
for the Contact Output Unit.
Electric Wires
The following electric wires are recommended.
Terminal Block Connector
Electric Wire Size
10-terminal
AWG 22 to 18 (0.32 to 0.82 mm
2
)
19-terminal
AWG 22 (0.32 mm
2
)
Note The allowable current capacity of electric wiring differs depending on factors
such as ambient temperature, insulation thickness, etc., so be sure to take these
factors into account when selecting electric wire.
Crimp Terminals
The terminals on the Power Supply Unit are M3.5, self-raising terminals with
screws.
Use crimp terminals for wiring. Do not connect bare stranded wires
directly to terminals. Tighten the terminal block screws to the torque of 0.8 N
S
m.
Use crimp terminals (M3.5) having the dimensions shown below.
7 mm max.
7 mm max.
For satisfying the EC Directives (Low-voltage Directives), provide reinforced
insulation or double insulation for the DC power supply used for the I/O Units.
Wiring
Section 3-2
Содержание C200HE-CPU -Z Series
Страница 1: ...Cat No W302 E1 09 Programmable Controllers C200HX CPUjj E ZE C200HG CPUjj E ZE C200HE CPUjj E ZE...
Страница 3: ...iv...
Страница 5: ...vi...
Страница 7: ......
Страница 23: ......
Страница 63: ......
Страница 109: ......
Страница 127: ......
Страница 212: ...Appendix B Specifications 197 Terminal Connections COM 12 to 24 VDC A0 A1 A2 A3 A4 A5 A6 A7 A8 A9 0 1 2 3 4 5 6 7 NC...
Страница 227: ......
Страница 233: ......