Appendix B
Specifications
211
Specifications
Item
C200H-B7A12
C200H-B7A02
C200H-B7A21
C200H-B7A22
I/O points
32 input points or
30 input points and 2
error inputs
32 output points
16 output points and
16 input points or
15 input 1
error input
32 output points and
32 input points or
30 input 2
error inputs
Transmission
method
One-way distributed multiplex transmission
Transmission
distance (see
note 1)
Standard:
500 m max.
High-speed:
100 m max.
Transmission
delay
Standard:
Typ. 19.2 ms, 31 ms max.
High-speed:
Typ. 3 ms, 5 ms max.
Minimum input
time (see note
2, 3)
Standard:
16 ms
High-speed:
2.4 ms
Internal current
consumption
5 VDC, 100 mA max.
External power
supply (see
12 to 24 VDC
±
10%
supply (see
note 4)
0.05 A min.
0.06 A min.
0.05 A min.
0.08 A min.
Weight
300 g max.
Dimensions
35 x 130 x 128 mm (W x H x D)
Note 1. The transmission distance also depends on whether a common or separate power supplies are used.
2. The minimum input time refers to the minimum time required for reading the input signals from the CPU
Unit.
3. The ON/OFF width of the signal transmitted from the CPU Unit to the Output Relay of the B7A Interface
Unit should be set to a value larger than the minimum input time.
4. The capacity of the external power supply does not include the capacity required by the B7A Link Termi-
nal.
Dimensions
145
128
Back-
plane
x
x
x
x
x
x
x
x
35
130
Содержание C200HE-CPU -Z Series
Страница 1: ...Cat No W302 E1 09 Programmable Controllers C200HX CPUjj E ZE C200HG CPUjj E ZE C200HE CPUjj E ZE...
Страница 3: ...iv...
Страница 5: ...vi...
Страница 7: ......
Страница 23: ......
Страница 63: ......
Страница 109: ......
Страница 127: ......
Страница 212: ...Appendix B Specifications 197 Terminal Connections COM 12 to 24 VDC A0 A1 A2 A3 A4 A5 A6 A7 A8 A9 0 1 2 3 4 5 6 7 NC...
Страница 227: ......
Страница 233: ......